4
How to use
-91-
No.PS
※※
-OMW0009-A
IO-Link Specifications
■
Outline of IO-Link functions
○Communication function
This product can check the distance measurement display value (guideline), the pressure measurement
value, diagnostic information and switch output status using cyclic data communication via the IO-Link
system.
○Product status monitoring function
This function monitors the product status via the IO-Link communication.
•Detects the error status (internal hardware error, OUT2 short-circuit).
•Detects the warning conditions (product internal temperature error, measurement pressure error).
○Data storage function
The Data storage function stores the IO-Link device parameter settings to the IO-Link master.
With the IO-Link data storage function, the IO-Link device can be replaced easily without re-setting the
equipment construction or setting parameters
When the device parameters are set and downloaded to the device using the IO-Link setting tool, the
parameters in the downloaded device will be activated.
After that, these parameters are uploaded to the data storage in the master by stem command (back-up
communication command).
When the device is replaced with the same type of IO-Link device due to failure, the parameter settings
stored in the master are downloaded automatically, device can be operated with the parameter settings of
the previous device.
Device parameter setting is applicable to 3 types of back-up levels of the master setting ("Inactive",
"back-up/Restore", "Restore").
"Back-up" implies the activation of upload and "restore" implies download.
■
Communication specifications
IO-Link type
Device
IO-Link version
V1.1
Communication speed
COM2 (38.4 kbps)
Min. cycle time
4.2 ms
Process data length
Input Data: 8 byte, Output Data: 0 byte
On request data communication
Available
Data storage function
Available
Event function
Available
Содержание ISA3-F series
Страница 1: ...No PS OMW0009 A PRODUCT NAME Digital Gap Checker compatible MODEL Series Product Number ISA3 series ...
Страница 10: ...2 About this product 9 No PS OMW0009 A With control unit ...
Страница 23: ...2 About this product 22 No PS OMW0009 A ISA3 Without control unit DIN rail mounting ...
Страница 24: ...2 About this product 23 No PS OMW0009 A ISA3 B L1 3 5 7 With control unit Bracket mounting ...
Страница 25: ...2 About this product 24 No PS OMW0009 A ISA3 B R1 3 5 7 ISA3 B R0 2 4 6 8 ISA3 B LN ISA3 B RN ...
Страница 42: ...3 Installation 41 No PS OMW0009 A Part structure Without control unit ...
Страница 43: ...3 Installation 42 No PS OMW0009 A With control unit Supply port Left side ...
Страница 44: ...3 Installation 43 No PS OMW0009 A With control unit Supply port Right side ...
Страница 115: ...5 Troubleshooting 114 No PS OMW0009 A Relationship between supply pressure and display ...