HRX-OM-R026
Chapter 4 Starting the Product
4.3
Preparation of circulating fluid
HRSH Series
4-6
4.
Press the [RESET] key (
[▼] and [▲] keys simultaneously) to reset the alarm.
The alarm (tank fluid level is low) is reset, and the [ALARM] lamp and [ ] lamp are
turned off.
The display returns to the initial screen of the main menu: “Circulating fluid
temp. / Circulating fluid
set temp.” Press the [PUMP] key (press [RUN/STOP] key and
[MENU] key simultaneously) to start independent operation of the pump.
Fig. 4-7 Alarm release
5.
Repeat steps 1 to 4 to
supply the circulating fluid to the customer’s equipment and
piping.
The tank level must be “H” on the tank liquid level indicator.
Be sure to reset the alarm on the operation display panel of the alarm.
Alarm reset
is not accepted from any screen except the alarm display menu. Refer to 5.2.1 Key
operations.
Press together
(
0
.
7
i
n
)
(
0
.
7
i
n
)
(
0
.
7
i
n
)
OFF
OFF
Содержание HRSH090-A
Страница 8: ...HRX OM R026 Contents HRSH Series ...
Страница 20: ...HRX OM R026 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRSH Series 2 6 ...
Страница 52: ...HRX OM R026 Chapter 3 Transport and Setting Up 3 6 Option J Piping of Automatic fluid filling HRSH Series 3 32 ...
Страница 62: ...HRX OM R026 Chapter 4 Starting the Product 4 6 Adjustment of Circulating Fluid flow rate HRSH Series 4 10 ...
Страница 146: ...HRX OM R026 Chapter 5 Display and setting of various functions 5 21 Communication function HRSH Series 5 84 ...
Страница 170: ...HRX OM R026 Chapter 8 Control Inspection and Cleaning 8 4 Stop for a Long Time HRSH Series 8 10 ...
Страница 188: ...HRX OM R026 Chapter 9 Documents 9 8 Daily Check Sheet HRSH Series 9 18 ...
Страница 191: ......