HRX-OM-R026
Chapter 3 Transport and Setting Up
3.3
Installation
HRSH Series
3-12
Power supply cable and Earth Leakage Breaker
Prepare the power supply shown in the following table. For the connection
between the product and power supply, use the power supply cable and
earth leakage breaker shown below.
Table 3-4 Power supply cable and Earth Leakage Breaker(Recommended
)
Model
Power
supply
voltage
Terminal
block
screw
diameter
Recomme
nded
crimp
terminal
Cable qty. x
size*2
Earth leakage
breaker *1
Rated
current
[A]
Sensitivity
of leak
current
[mA]
HRSH090-A
-20-
HRSH090-W
-20-
AC200/
200-230V
50/60Hz
3phase
M5
R5.5-5
4 cores x AWG10
(4 cores x 5.5mm
2
)
*including ground
30
30
HRSH090-A
-40-
HRSH090-W
-40-
AC380-415V
50/60Hz
3phase
R5.5-5
(Power
supply)
R14-5
(Grounding
cable)
3 x 5.5
mm
2
(3 x AWG10)
(Power supply)
1 x 14 mm
2
(1 x AWG6)
(Grounding cable)
20
1: A specified earth leakage breaker is installed for option B [Earth leakage breaker] or option S
[CE/UL] of each model.
If the product is not option B [Earth leakage breaker] or option S [CE/UL], please prepare an earth
leakage breaker by the customer side.
A specified earth leakage breaker is installed for HRSH090-
-40-
.
2: Please select the proper size of cable according to an actual condition.
3.3.3
Preparation and wiring of power supply cable
The electrical facilities should be installed and wired in
accordance with local laws and regulations of each country and by
a person who has knowledge and experience.
Check the power supply. Operation with voltages, capacities and
frequencies other than the specified values can cause fire and
electrical shock.
Wire with an applicable cable size and terminal. Forcibly mounting
with an unsuitable size cable may result in heat generation or fire.
Содержание HRSH090-A
Страница 8: ...HRX OM R026 Contents HRSH Series ...
Страница 20: ...HRX OM R026 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRSH Series 2 6 ...
Страница 52: ...HRX OM R026 Chapter 3 Transport and Setting Up 3 6 Option J Piping of Automatic fluid filling HRSH Series 3 32 ...
Страница 62: ...HRX OM R026 Chapter 4 Starting the Product 4 6 Adjustment of Circulating Fluid flow rate HRSH Series 4 10 ...
Страница 146: ...HRX OM R026 Chapter 5 Display and setting of various functions 5 21 Communication function HRSH Series 5 84 ...
Страница 170: ...HRX OM R026 Chapter 8 Control Inspection and Cleaning 8 4 Stop for a Long Time HRSH Series 8 10 ...
Страница 188: ...HRX OM R026 Chapter 9 Documents 9 8 Daily Check Sheet HRSH Series 9 18 ...
Страница 191: ......