HRX-OM-R026
Chapter 8 Control, Inspection and Cleaning
HRSH Series
8.2
Inspection and Cleaning
8-5
8.2.4
Inspection every 6 months
Check for water leakage from pump
Remove the panel and check the pump for excessive leakage. If the
leakage is found, replace the mechanical seal. Order the mechanical seal
described in “8.3Consumables” as a service part.
Fig. 8-3
Check for water leakage from pump
Leakage from the mechanical seal
It is impossible to prevent the leakage from the mechanical seal completely
because of its structure. Although the leakage is described as 3cc/hr or less.
The recommend life time of the mechanical seal before needing replacement
is 6000 to 8000 hours.
Leakage was found here
Содержание HRSH090-A
Страница 8: ...HRX OM R026 Contents HRSH Series ...
Страница 20: ...HRX OM R026 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRSH Series 2 6 ...
Страница 52: ...HRX OM R026 Chapter 3 Transport and Setting Up 3 6 Option J Piping of Automatic fluid filling HRSH Series 3 32 ...
Страница 62: ...HRX OM R026 Chapter 4 Starting the Product 4 6 Adjustment of Circulating Fluid flow rate HRSH Series 4 10 ...
Страница 146: ...HRX OM R026 Chapter 5 Display and setting of various functions 5 21 Communication function HRSH Series 5 84 ...
Страница 170: ...HRX OM R026 Chapter 8 Control Inspection and Cleaning 8 4 Stop for a Long Time HRSH Series 8 10 ...
Страница 188: ...HRX OM R026 Chapter 9 Documents 9 8 Daily Check Sheet HRSH Series 9 18 ...
Страница 191: ......