HRX-OM-R026
Chapter 9 Documents
HRSH Series
9.1 Specifications
9-5
9.1.5
Communication specification
Regarding the communication specification, refer to the operation manual
communication function, HRX-OM-R027.
Contact input/output
Table 9-3 Specifications List
Item
Specification
Connector type
M3 terminal block
Contact
input
signal
Insulation method
Photo coupler
Rated input voltage
DC24V
Input voltage range
DC 21.6V to 26.4V
Rated input current
5mA TYP
Input impedance
4.7kΩ
Contact
output
signal
Rated load voltage
AC48V or less/DC30V or less
Maximum load current
AC/DC 500mA (Resistance load)
Minimum load current
DC5V 10mA
DC24V power supply output
DC24V±10
%
500mA MAX (No inductive load)
Circuit
structure
diagram
4.7k
Ω
Intern
al
circui
t
DC24V
24VCOM
1k
Ω
4.7k
Ω
1k
Ω
---
0
8
1
9
2
10
3
11
4
12
13
14
15
7
5
6
DC24V output
(500mA or less)*1
24VCOM output
Contact output signal 3
Contact input signal 1
Contact output signal 1
Contact output signal 2
Contact input signal 2
Alarm status signal output
Run/stop signal input
Operation status signal output
Remote status signal output
Thermo-chiller side
Cuctomer's equipment side
Signal description
Default setting
1
No inductive load.
Содержание HRSH090-A
Страница 8: ...HRX OM R026 Contents HRSH Series ...
Страница 20: ...HRX OM R026 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRSH Series 2 6 ...
Страница 52: ...HRX OM R026 Chapter 3 Transport and Setting Up 3 6 Option J Piping of Automatic fluid filling HRSH Series 3 32 ...
Страница 62: ...HRX OM R026 Chapter 4 Starting the Product 4 6 Adjustment of Circulating Fluid flow rate HRSH Series 4 10 ...
Страница 146: ...HRX OM R026 Chapter 5 Display and setting of various functions 5 21 Communication function HRSH Series 5 84 ...
Страница 170: ...HRX OM R026 Chapter 8 Control Inspection and Cleaning 8 4 Stop for a Long Time HRSH Series 8 10 ...
Страница 188: ...HRX OM R026 Chapter 9 Documents 9 8 Daily Check Sheet HRSH Series 9 18 ...
Страница 191: ......