HRX-OM-R026
Chapter 7 Alarm indication and trouble shooting
HRSH Series
7.3
Troubleshooting
7-7
Table 7-3 Alarm code list and Troubleshooting (3/3)
Code
Alarm name
Alarm
operation*1
(Default
setting)
Cause / Remedy
(Press the reset key after eliminating the
cause.)
AL40
Dust-proof
filter
maintenance
OFF
Notice
of
the
periodical
maintenance.
Clean
the
dust-proof filter.
Every 500h
3
AL41
Power stoppage
A.STP
The power was shut off during running.
Restart after checking the power supply.
AL42
Compressor waiting
A.RUN
The system is waiting for the compressor to
be ready to run. Wait for a while.
Will be automatically released after running.
AL43
2 Fan breaker trip
P.RUN
Check that there is
no power failure
such as ground
fault, short circuit,
voltage fluctuation,
abnormal
interphase voltage,
open phase, surge.
Release the fan breaker
trip referring to [6.3.2
How to release the fan
breaker trip].
AL44
2 Fan inverter error
P.RUN
AL45
1
Compressor
breaker
trip
P.RUN
Keep
the [▼] and [▲] keys
of the operation display
panel
pressed
down
simultaneously
for
10
seconds to reset. After
resetting
AL48,
WAIT(
)
will be
displayed and the product
cannot run for 40 seconds.
Restart 40 seconds later
after resetting.
AL46
Compressor
inverter
error
P.RUN
AL47
1 Pump breaker trip
A.STP
AL48
Pump inverter error
A.STP
AL47
4
Internal
unit
fan
stoppage
A.RUN
Internal unit fan failure. Ask for service for the
internal unit fan.
1: This alarm does not occur on the product of power specification
‘-20’. (Except option S.)
2: This alarm does not occur on the product of water cooled type.
3: Change the setting within the range of 1 to 9999.
4: This alarm does not occur on the product of air cooled type.
Содержание HRSH090-A
Страница 8: ...HRX OM R026 Contents HRSH Series ...
Страница 20: ...HRX OM R026 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRSH Series 2 6 ...
Страница 52: ...HRX OM R026 Chapter 3 Transport and Setting Up 3 6 Option J Piping of Automatic fluid filling HRSH Series 3 32 ...
Страница 62: ...HRX OM R026 Chapter 4 Starting the Product 4 6 Adjustment of Circulating Fluid flow rate HRSH Series 4 10 ...
Страница 146: ...HRX OM R026 Chapter 5 Display and setting of various functions 5 21 Communication function HRSH Series 5 84 ...
Страница 170: ...HRX OM R026 Chapter 8 Control Inspection and Cleaning 8 4 Stop for a Long Time HRSH Series 8 10 ...
Страница 188: ...HRX OM R026 Chapter 9 Documents 9 8 Daily Check Sheet HRSH Series 9 18 ...
Страница 191: ......