HRX-OM-W058
Chapter 5 Display and setting of various functions
HRS-R Series
5.16
Alarm customize function
5-35
●AL19
Communication error (Refer to Table 5.16-12 and Table 5.16-13)
Operation: When this alarm signal is output, user can choose to
stop/continue operation, or not to detect this alarm.
“Not to detect “is default setting.
Threshold change: Time at which this alarm is generated can be
changed.
“30sec" is default setting.
●AL31
Contact input signal 1 detection(Refer toTable 5.16-14)
Operation: When this alarm signal is output, user can choose to
stop/continue operation, or not to detect this alarm.
"Operation continue" is default setting.
●AL32
Contact input signal 2 detection (Refer to Table 5.16-15)
Operation: When this alarm signal is output, user can choose to
stop/continue operation, or not to detect this alarm.
"Operation continue" is default setting.
●AL21
DC fuse cut
(
Refer to Table 5.16-16
Operation: When this alarm signal is output, user can choose to
stop/continue the operation.
"Operation stop" is default setting.
"Operation stop" is the
default setting for alarm “AL01 Low tank level”.
If the customer changes this setting to continue operation, fill the
circulating fluid immediately after the alarm is generated.Operation
without filling the circulating fluid leads to cause malfunction.
Содержание HRS018-A
Страница 16: ...HRX OM W058 Chapter 1 Safety Instructions 1 8 Material Safety Data Sheet MSDS HRS R Series 1 10...
Страница 22: ...HRX OM W058 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRS R Series 2 6...
Страница 50: ...HRX OM W058 Chapter 3 Transport and Setting Up 3 7 Wiring of external switch HRS R Series 3 28...
Страница 130: ...HRX OM W058 Chapter 6 Option Optional Accessories 6 5 Option V Stainless steel enclosure HRS R Series 6 4...
Страница 146: ...HRX OM W058 Chapter 8 Control Inspection and Cleaning 8 4 Stop for a Long Time HRS R Series 8 10...
Страница 161: ......