HRX-OM-W058
Chapter 5 Display and setting of various functions
HRS-R Series
5.2
Function
5-5
Table 5.2-2 List of parameter (2/3)
Display
Item
Initial value
(Default setting)
Reference
page
Category
Alarm buzzer sound
ON
Alarm setting
menu
Changing of low tank level
A.STP
Changing of circulating fluid discharge
temperature rise
A.RUN
Detection temperature for circulating
fluid discharge temperature rise
45.0
o
C(113.0
o
F)
Changing of circulating fluid discharge
temperature drop
A.RUN
Detection temperature for circulating
fluid discharge temperature drop
1.0
o
C(33.8
o
F)
Changing of circulating fluid discharge
pressure rise
A.RUN
Detection pressure for circulating fluid
discharge pressure rise
0.30MPa(44PSI)*
1
Changing of circulating fluid discharge
pressure drop
A.RUN
Detection pressure for circulating fluid
discharge pressure drop
0.05MPa(7PSI)
Changing of communication error
OFF
The monitoring time of communication
error
30 sec
Unused
-
Changing of Contact input signal 2
detection
A.STP
Changing of DC line fuse cut
A.STP
Changing of water leakage
A.STP
Changing of upper limit of electric
resistivity/conductivity
OFF
Upper
limit
of
electric
resistivity/conductivity
□
Changing of lower limit of electric
resistivity/conductivity
OFF
Lower
limit
of
electric
resistivity/conductivity
□
Temperature alarm
Monitoring method
0
Monitoring start timer
- - - -
Range over
Detection timer
5
Communication mode
LOC
Communication
setting menu
Se
ria
l
c
ommu
n
ica
tio
n
Serial protocol
MDBS
Communication specifications
485
RS-485 terminal
OFF
Mod
bus
Slave address
1
Communication
speed
19.2
S
imp
le
commu
ni
c
ation
pro
toco
l
Slave address
1
Communication
speed
9.6
BCC
ON
Data length
8BIT
Parity check
NON
Stop bit length
2BIT
Response delay time
0
Communication
range
RW
Содержание HRS018-A
Страница 16: ...HRX OM W058 Chapter 1 Safety Instructions 1 8 Material Safety Data Sheet MSDS HRS R Series 1 10...
Страница 22: ...HRX OM W058 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRS R Series 2 6...
Страница 50: ...HRX OM W058 Chapter 3 Transport and Setting Up 3 7 Wiring of external switch HRS R Series 3 28...
Страница 130: ...HRX OM W058 Chapter 6 Option Optional Accessories 6 5 Option V Stainless steel enclosure HRS R Series 6 4...
Страница 146: ...HRX OM W058 Chapter 8 Control Inspection and Cleaning 8 4 Stop for a Long Time HRS R Series 8 10...
Страница 161: ......