HRX-OM-W058
Chapter 6 Option
・
Optional Accessories
HRS-R Series
6.4
Option T [High-pressure pump]
6-3
6.4 Option T [High-pressure pump]
6.4.1
Option T [High-pressure pump]
With option T (high pressure pump mounted), the discharge pressure is
raised.
The high pressure pump uses a mechanical seal.
Thermo Chiller makes AL28 alarm when driving time is passed a
recommended preventive maintenance hours. Please contact to service
center to ask for maintenance of the pump and mechanical seal.
Applicable model
-
-20-T-R
Pump
Rated flow (50/60 Hz)
Note 1),2)
L/min
10 (0.35 MPa) /14 (0.35 MPa)
Maximum flow rate (50/60 Hz)
L/min
17 / 20
Maximum pump head (50/60 Hz)
m
70
Output
W
610
Recommended earth leakage breaker capacity
A
15
Cooling capacity
Note 3)
W
The cooling capacity reduces approximately 300 W
from the value in the catalog
Note 1) The capacity at Thermo-chiller outlet.
Note 2) Required minimum flow rate for cooling capacity or maintaining the temperature stability.
Note 3) Cooling capacity decreasing due to bigger pump motor.
6.5 Option V [Stainless steel enclosure]
6.5.1
Option V [Stainless steel enclosure]
With option V , the materials of enclosures are changed to stainless steel.
Enclosures: Front panel, Right side panel, Left side panel, Rear panel,
upper panel and bottom base.
Содержание HRS018-A
Страница 16: ...HRX OM W058 Chapter 1 Safety Instructions 1 8 Material Safety Data Sheet MSDS HRS R Series 1 10...
Страница 22: ...HRX OM W058 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRS R Series 2 6...
Страница 50: ...HRX OM W058 Chapter 3 Transport and Setting Up 3 7 Wiring of external switch HRS R Series 3 28...
Страница 130: ...HRX OM W058 Chapter 6 Option Optional Accessories 6 5 Option V Stainless steel enclosure HRS R Series 6 4...
Страница 146: ...HRX OM W058 Chapter 8 Control Inspection and Cleaning 8 4 Stop for a Long Time HRS R Series 8 10...
Страница 161: ......