HRX-OM-W058
Chapter 4 Starting the Product
4.5
Check items after starting
HRS-R Series
4-8
If the valve locates in circulating piping, do not fully close the valve
(0L/min). The pump may be damaged.
4.5 Check items after starting
Check the following items after starting the product.
There is no leakage from piping.
There is no drain of circulating fluid from the tank drain port.
The circulating fluid pressure is within the specified range.
The tank level is within the specified range.
4.6 Adjustment of Circulating Fluid
Flow adjustment
If the flow rate is less than 7L/min it will not be able to achieve the specified
cooling capacity. The adjustment of flow rate should be performed using a
manual bypass valve and monitoring the pressure or flow rate in the
customer’s device, referring to the recommended piping flow shown in
Figure 3-12, until they reach the required value.
When an Alarm is seen, press the [STOP] button and then turn off the
breaker of the user’s power supply to isolate the product.
Содержание HRS018-A
Страница 16: ...HRX OM W058 Chapter 1 Safety Instructions 1 8 Material Safety Data Sheet MSDS HRS R Series 1 10...
Страница 22: ...HRX OM W058 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRS R Series 2 6...
Страница 50: ...HRX OM W058 Chapter 3 Transport and Setting Up 3 7 Wiring of external switch HRS R Series 3 28...
Страница 130: ...HRX OM W058 Chapter 6 Option Optional Accessories 6 5 Option V Stainless steel enclosure HRS R Series 6 4...
Страница 146: ...HRX OM W058 Chapter 8 Control Inspection and Cleaning 8 4 Stop for a Long Time HRS R Series 8 10...
Страница 161: ......