HRX-OM-W058
Chapter 5 Display and setting of various functions
HRS-R Series
5.5
Inspection monitor menu
5-11
Check of the pressure of the lower pressure side of the refrigerant circuit
6.
Press the [SEL] key once.
The pressure of lower pressure refrigerant circuit is displayed on the digital display.
Displays the pressure of the lower pressure side of the refrigerant circuit.
Check of the electric resistivity/conductivity
7.
Press the [SEL] key once.
The electric resistivity/conductivity is displayed on the digital display.
This function is not available for this product.
Check of the accumulated operation time of the pump
8.
Press the [SEL] key once.
The accumulated operation time of the pump is displayed on the digital display.
Displays the accumulated operation time of the pump. Refer to the table below for the
display.
Table 5.5-2 List of time display
Cumulative time
Indicated value
0h to 999h
to
1,000h to 99,999h
to
100,000h
Return to
AL28 Pump maintenance alarm is generated when the accumulated operation time of the
pump reaches 20,000 hours (
) or more.
【
In the case Option T, 8,000 hours
(
) or more
】
For details, refer to Chapter 7 Alarm indication and trouble shooting
PV
SV
PV
SV
PV
SV
Содержание HRS018-A
Страница 16: ...HRX OM W058 Chapter 1 Safety Instructions 1 8 Material Safety Data Sheet MSDS HRS R Series 1 10...
Страница 22: ...HRX OM W058 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRS R Series 2 6...
Страница 50: ...HRX OM W058 Chapter 3 Transport and Setting Up 3 7 Wiring of external switch HRS R Series 3 28...
Страница 130: ...HRX OM W058 Chapter 6 Option Optional Accessories 6 5 Option V Stainless steel enclosure HRS R Series 6 4...
Страница 146: ...HRX OM W058 Chapter 8 Control Inspection and Cleaning 8 4 Stop for a Long Time HRS R Series 8 10...
Страница 161: ......