HRX-OM-W058
Chapter 5 Display and setting of various functions
HRS-R Series
5.19
Communication function
5-61
34.
Select contact input signal 1 delay timer of reading from the table below with
[▲] key or
[▼] key, and confirm by pressing “SEL”.
Table 5.19-18
List of set value
Set value
Explanation
Initial value
(Default setting)
Setting and checking are not available unless
contact input singal 1 is external switch signal
input (N.O. type or N.C. type).
to
Setting of contact input signal 1 delay timer of
reading.
Set range is 0 to 300 sec.
Contact input signal 1 OFF detection timer
Setting and checking
35.
Press the [SEL] key once.
The set screen of the contact input signal 1 OFF detection timer is displayed on the
digital display.
36.
Select contact input signal 1 OFF detection timer from the table below with
[▲] key or
[▼] key, and confirm by pressing “SEL”.
Table 5.19-19
List of set value
Set value
Explanation
Initial value
(Default setting)
Setting and checking are not available unless
contact input singal 1 is external switch signal
input (N.O. type or N.C. type).
to
Setting of contact input signal 1 OFF
detection timer
Set range is 0 to 10sec.
Contact input signal 2 Setting and checking
37.
Press the [SEL] key once.
The set screen of contact input signal 2 is displayed on the digital display.
PV
SV
PV
SV
Содержание HRS018-A
Страница 16: ...HRX OM W058 Chapter 1 Safety Instructions 1 8 Material Safety Data Sheet MSDS HRS R Series 1 10...
Страница 22: ...HRX OM W058 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRS R Series 2 6...
Страница 50: ...HRX OM W058 Chapter 3 Transport and Setting Up 3 7 Wiring of external switch HRS R Series 3 28...
Страница 130: ...HRX OM W058 Chapter 6 Option Optional Accessories 6 5 Option V Stainless steel enclosure HRS R Series 6 4...
Страница 146: ...HRX OM W058 Chapter 8 Control Inspection and Cleaning 8 4 Stop for a Long Time HRS R Series 8 10...
Страница 161: ......