TROUBLESHOOTING

 

DRIVE FAULT / ENCODER FLT 

1.

 

The most common fault at startup with a Magnetek drive is the 
Encoder fault. Perform the following checks to correct this fault: 

a.

 

Check  for  a  solid 

shield-to-ground

  connection  at  the  motor 

and drive. 

b.

 

Check for correct colored encoder wires to the terminals. 

c.

 

Verify that “C1 - Encoder Select” is set to “

Axial Flux

”. 

d.

 

Swap A+ / A- on terminal TB2 – #1 (A) and #2 (/A). 

i.

 

After changing any encoder wiring the Encoder Alignment 
must be ran again (See page 6).  

BRAKE NOT LIFTING 

1.

 

If the brake is not picking make sure that it is wired according to 
Sheet 5 – Brakes and verify that the EB terminal is jumped to the 
terminal listed on “Sheet 01 – Getting Started”. If it has the proper 
voltage check the following: 

a.

 

During a run command, check for DC voltage between points 
K1 / K2 and J1 / J2. Verify the voltages are also at the Brake 
Coil(s) when commanded to pick. 

b.

 

Verify that the voltages match the Brake Coil voltages shown 
on “Sheet 1: Getting Started” table. 

WRONG DIRECTION 

1.

 

If the car is moving in the wrong direction: 

a.

 

On  the  Smartrise  controller  board  make  sure  that  IO  521 
comes  on  when  commanding  the 

UP

  direction  and  IO  522 

comes on when commanding the 

DOWN

 direction.  

b.

 

Change the direction of the motor in the drive by going to “C1 
–  Motor  Rotation”  and  toggling  between  FORWARD/ 
REVERSE. 

c.

 

Swap two of the motor leads (T1 with T2). After swapping the 
motor  wires  it  may  be  necessary  to  change  C1  –  Motor 
Rotation again. Run the U12 Auto Tune again. 

 

 

Содержание Magnetek HPV900AF

Страница 1: ...DRIVE STARTUP MANUAL Magnetek HPV900AF Drive PM Motor Installation www smartrise us 2601 Fair Oaks Blvd Sacramento CA 95864 916 457 5129...

Страница 2: ...AMETER LOCATION REFERENCE ADJUST A0 DRIVE A1 Encoder Pulses Follow procedure in Axial Flux manual Pg 9 POWER CONVERT A4 Input L L Volts MOTOR A5 Rated Mtr Power Kw Rated Mtr Volts VAC Rated Exit Freq...

Страница 3: ...side of the incoming water main To a grounding rod that has been driven into the pit flooring The controller has a common ground bus terminal connection All grounds need to land at this common point i...

Страница 4: ...l blocks Jump EB to the terminal listed in the Construction box located on Sheet 01 Getting Started and connect either the rope gripper or sheave brake to EBR if installed Motor Leads Connect motor le...

Страница 5: ...ween M24 and the IOs listed on Sheet 1 Getting Started Construction Install jumpers between M24 any additional IO s if required Pre Transfer Emergency Power Governor IMPORTANT REMOVE FACTORY WIRES ON...

Страница 6: ...Check off box when complete Toggle the Inspection Normal switch to the INSP position Set BYPASS TERM LIMITS to YES o On the Smartrise Machine Room controller board press the Left Arrow ESC button seve...

Страница 7: ...to YES o Use the RIGHT Arrow key and move the asterix under the word SAVE and press enter o Hit the LEFT Arrow ESC button several times to get to the MAIN SCREEN Verify the LCD displays Construction M...

Страница 8: ...to YES but DON T PRESS THE ENTER BUTTON YET Press and hold the M contactor button in Press the Enter button on the drive to start the alignment ENCODER ALIGNMENT NON ROTATIONAL Check off box when comp...

Страница 9: ...PARAMETER DESCRIPTION CHOICES AUTOTUNE SELECT ALLOW AUTOTUNE TO RUN DISABLE ON RUN YES ROTOR ALIGN U10 PARAMETER DESCRIPTION CHOICES ALIGNMENT ALLOW ALIGNMENT TO BE PERFORMED ENABLE DISABLE BEGIN ALIG...

Страница 10: ...ions Proper Direction Make sure the car is moving in the same direction as the control switch on the Run Bug o Go to Troubleshooting Wrong Direction for corrective actions At Speed Make sure that the...

Страница 11: ...the terminal listed on Sheet 01 Getting Started If it has the proper voltage check the following a During a run command check for DC voltage between points K1 K2 and J1 J2 Verify the voltages are als...

Страница 12: ...5 that conflicts with drive software 1 Unplug the CAT5 cable from the DRIVE port on the machine room SRU board This will restore access to the HPV LCD screen 2 Go to A5 Motor Parameters Motor Poles an...

Страница 13: ...13 APPENDIX Terminal Locations Encoder wiring terminals GND terminals Main Line terminals L1 L2 L3 Motor terminals T1 T2 T3 Brake terminal block J1 J2 K1 K2 Terminal TB1 J1 J2...

Отзывы: