HGM9510 GENSET PARALLEL UNIT
HGM9510 Genset Parallel Unit ISSUE 2013-08-06 Version 1.1 Page 33 of 65
No.
Items
Parameters
Defaults
Description
this value. Detecting only after safety
delay is over. The delay value (default:
3s) also can be set.
4
Low OP Warn
(0~1000)kPa
124
Warn when oil pressure higher than this
value. Detecting only after safety delay
is over. The delay value (default: 5s) and
return value (default: 138) also can be
set.
Liquid Level Sensor
1
Curve Type
(0~15)
0
Not used. See form 4
Flexible Sensor 1
1
Flexible Sensor 1
Setting
(0~1)
0
0: Disable 1: Enable; (can be set as
temperature/pressure/liquid
lever
sensor).
Flexible Sensor 2
1
Flexible Sensor 2
Setting
(0~1)
0
0: Disable; 1: Enable; (can be set as
temperature/pressure/liquid
lever
sensor).
Flexible Input Ports
Flexible Input Port 1
1
Contents Setting
(0~50)
31
Remote start (demand). See form 3
2
Active Type
(0~1)
0
0: Closed to active
1: Open to active
Flexible Input Port 2
1
Contents Setting
(0~50)
27
Low oil pressure shutdown
See form 3
2
Active Type
(0~1)
0
0: Closed to active
1: Open to active
Flexible Input Port 3
1
Contents Setting
(0~50)
26
High temperature shutdown
See form 3
2
Active Type
(0~1)
0
0: Closed to active
1: Open to active
Flexible Input Port 4
1
Contents Setting
(0~50)
13
Gen Closed. See form 3
2
Active Type
(0~1)
0
0: Closed to active
1: Open to active
Flexible Input Port 5
1
Contents Setting
(0~50)
0
User defined. See form 3
2
Active Type
(0~1)
0
0: Closed to active
1: Open to active
3
Arming
(0~3)
3
0: From safety on 1: From starting
2: Always 3:Never
4
Active Actions
(0~4)
4
0: Warn; 1: Shutdown; 2:Trip and stop