HGM9510 GENSET PARALLEL UNIT
HGM9510 Genset Parallel Unit ISSUE 2013-08-06 Version 1.1 Page 11 of 65
Mute/Reset
Alarm
Alarming sound off; If trip alarm occurs, pressing the button
at least 3 seconds can reset this alarm.
Close
Close breaker in manual mode.
Open
Open breaker in manual mode.
Up/Increase
1) Screen scroll;
2) Up cursor and increase value in setting menu.
Down/Decrease
1) Screen scroll;
2) Down cursor and decrease value in setting menu.
Left
1) Screen scroll;
2) Left move cursor in setting menu.
Right
1) Screen scroll;
2) Right move cursor in setting menu.
Set/Confirm
Select viewing area.
Exit
1)Return to main menu;
2) Return to previous menu in setting menu.
NOTE
: Press
and
simultaneously in manual mode will force generator to
crank. Successful start will not be judged according to crank disconnect conditions, operator will
have to crank the starter motor manually; when operator decides that the engine has fired, he/she
should release the button and start output will be deactivated, safety on delay will be initiated.
WARNING:
Default password is 00318, user can change it in case of others change the
advanced parameters setting. Please clearly remember the password after changing. If you forget
it, please contact Smartgen services and send all information in the controller page of “
ABOUT
” to
us.
5.3 LCD DISPLAY
5.3.1 MAIN DISPLAY
Main screen show pages; use
to scroll the pages and
to scroll the screen.
★
Main Screen
, including as below,
Gen: voltage, frequency, current, active power, reactive power
Bus: voltage, frequency
Engine: speed, temperature, oil pressure
Some status
★
Status
, including as below,