NO.
Functions
Cable
Size
Remark
49
CT A-phase sensing
input
1.5mm
2
Outside connected to secondary coil of current
transformer(rated 5A)
50
CT B-phase sensing
input
1.5mm
2
Outside connected to secondary coil of current
transformer(rated 5A)
51
CT C-phase sensing
input
1.5mm
2
Outside connected to secondary coil of current
transformer(rated 5A)
52
CT COM
1.5mm
2
See following installation instruction
56
Aux. sensor 1
1.0mm
2
Connect to temperature, oil
pressure or fuel level sensors.
Details see form
4
57
Aux. sensor 2
1.0mm
2
58
Oil pressure
1.0mm
2
Connect to oil pressure sensor.
59
Engine Temp.
1.0mm
2
Connect to temperature Sensor.
60
Fuel level
1.0mm
2
Connect to fuel level sensor.
61
Sensor COM
/
A public terminal of sensor, (B-) has already
connected internal.
NOTE:
USB ports in controller rear panel are configurable parameter ports, user can directly
program controller via PC.
NOTE:
in this manual for more products’ functions.