HGM8156 GENSET PARALLEL CONTROLLER USER MANUAL
HGM8156 Genset Parallel (With Mains) Controller 2019-09-10 Version 1.1 Page 32 of 44
No.
Type
Description
24
Reset
Maintenance
Alarm
Controller will set maintenance time and date as default when input is
active.
25-27 Reserved
28
Remote Start
(On Load)
In Auto mode, when input is active, genset can be started and takes
load after genset running normal; when input is inactive, genset will
stop automatically.
29
Remote Start
(Off Load)
In Auto mode, when input is active, genset can be started and takes
off load after genset running normal; when input is inactive, genset
will stop automatically.
30
Manual Start Aux
In Auto mode, when input is active, genset will start automatically;
when input is inactive, genset will stop automatically;
31
Remote Start
(On Demand)
In Auto mode, when input is active, genset will start/stop according to
load;
32
Remote Start Island
In Auto mode, when input is active, genset will start automatically and
takes load after normal running, mains unloads; when input is
inactive, mains takes load and genset unloads and stops
automatically;
33
Simulate Stop Button
An external button can be connected and pressed as the simulate
panel key.
34
Simulate Manual Button
35
Reserved
36
Simulate Auto Button
An external button can be connected and pressed as the simulate
panel key.
37
Simulate Start Button
38
Simulate
Bus
Close/Open Button
39
Simulate
Mains
Close/Open Button
40
Reserved
41-44 Reserved
45
Simulate Mains Normal
In Auto mode, when input is active, it means mains is normal;
46
Simulate
Mains
Abnormal
In Auto mode, when input is active, it means mains is abnormal;
47-55 Reserved