HGM8156 GENSET PARALLEL CONTROLLER USER MANUAL
HGM8156 Genset Parallel (With Mains) Controller 2019-09-10 Version 1.1 Page 20 of 44
No.
Functions
Cable Size
Remark
38
2.5mm
2
Public points of relay
Table 14.
39
Aux. output 6
2.5mm
2
Normally open outputs, rated 8A
40
2.5mm
2
Public points of relay
41
Mains
A-phase
voltage input
1.0mm
2
Connects to A-phase of mains(2A fuse is recommended)
42
Mains
B-phase
voltage input
1.0mm
2
Connects to B-phase of mains (2A fuse is recommended)
43
Mains
C-phase
voltage input
1.0mm
2
Connects to C-phase of mains (2A fuse is recommended)
44
Mains N-wire input
1.0mm
2
Connects to N-wire of mains
45
Gen Bus A-phase
voltage input
1.0mm
2
Connects to A-phase of gen bus output
(2A fuse is recommended)
46
Gen Bus B-phase
voltage input
1.0mm
2
Connects to B-phase of gen bus output
(2A fuse is recommended)
47
Gen Bus C-phase
voltage input
1.0mm
2
Connects to C-phase of gen bus output
(2A fuse is recommended)
48
Gen Bus N-wire
input
1.0mm
2
Connects to N-wire of gen bus output
49
CT A-phase input
1.5mm
2
Outside connects to secondary coil of CT (rated 5A)
50
CT B-phase input
1.5mm
2
Outside connects to secondary coil of CT (rated 5A)
51
CT C-phase input
1.5mm
2
Outside connects to secondary coil of CT (rated 5A)
52
CT COM
1.5mm
2
Refer to following installation instruction;
53
Gen Bus A-phase
current input
1.5mm
2
Outside connects secondary coil of CT (rated 5A)
54
1.5mm
2
55
Aux. Input 8
1.0mm
2
Ground connected is active (B-)
For details please
see Table 15.
56
Reserved
/
Reserved terminal; Please don't connect wires.
57
58
59
60
61
NOTE1:
USB port on back panel is parameter configuration port and can set controller on PC.
NOTE2:
Ethernet port on back panel is network monitoring port, and can monitor controller on PC.