HGM8156 GENSET PARALLEL CONTROLLER USER MANUAL
HGM8156 Genset Parallel (With Mains) Controller 2019-09-10 Version 1.1 Page 26 of 44
No.
Items
Range
Defaults
Description
Relay Output Port 1
1
Contents Setting
(0~239)
44
Generator OK.
2
Output Type
(0~1)
0
0:Normally open;
1:Normally close
Relay Output Port 2
1
Contents Setting
(0~239)
48
Common Alarm.
2
Output Type
(0~1)
0
0:Normally open;
1:Normally close
Relay Output Port 3
1
Contents Setting
(0~239)
46
Mains Normal Output
2
Output Type
(0~1)
0
0:Normally open;
1:Normally close
Relay Output Port 4
1
Contents Setting
(0~239)
47
Synchronizing
2
Output Type
(0~1)
0
0:Normally open;
1:Normally close
Relay Output Port 5
1
Contents Setting
(0~239)
31
Mains Close Output.
2
Output Type
(0~1)
0
0:Normally open;
1:Normally close
Relay Output Port 6
1
Contents Setting
(0~239)
29
Bus Close Output.
2
Output Type
(0~1)
0
0:Normally open;
1:Normally close
Relay Output Port 7
1
Contents Setting
(0~239)
32
Mains Open Output
2
Output Type
(0~1)
0
0:Normally open;
1:Normally close
Relay Output Port 8
1
Contents Setting
(0~239)
30
Bus Open Output
2
Output Type
(0~1)
0
0:Normally open;
1:Normally close
Sync Setting -Basic
1
Dead Bus Volt
(10-50)V
30
It is considered bus is dead when bus
voltage is lower than dead bus voltage.
2
Voltage Difference
(0-30)V
3
It is considered voltage synchronization
when the voltage difference between
generator
and
bus
is
lower
than
synchronization voltage difference.
3
Positive
Freq
Difference
(0-2.0)Hz
0.2
It is considered frequency synchronization
when the frequency difference between
generator and bus is less than positive
4
Negative
Freq (0-2.0)Hz
0.1