HGM8156 GENSET PARALLEL CONTROLLER USER MANUAL
HGM8156 Genset Parallel (With Mains) Controller 2019-09-10 Version 1.1 Page 21 of 44
8
SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS
8.1 CONTENTS AND SCOPES OF PARAMETERS
Table 13 Parameter Setting Contents and Range
No.
Items
Range
Defaults
Description
Mains Setting
1
AC System
(0-3)
0
0: 3P4W;
1: 3P3W;
2: 2P3W;
3: 1P2W;
2
Rated Voltage
(30-30000)V
230
Provide standard for mains over/under
voltage detection; it is primary voltage of CT;
When AC system is 3P3W, it is wire voltage;
for other systems, it is phase voltage;
3
Rated Frequency
(10.0-75.0)Hz
50.0
Provide standard for mains over/under
frequency detection;
4
Normal Time
(0-3600)s
10
Check time for mains from abnormal to
normal;
5
Abnormal Time
(0-3600)s
5
Check time for mains from normal to
abnormal;
6
PT Fitted
(0-1)
0
0: Disable
1: Enable
7
Over Voltage
(0-200)%
120
Rated voltage percentage; return value
(default 116%) and delay value (default 5s)
can also be set;
8
Under Voltage
(0-200)%
80
Rated voltage percentage; return value
(default 84%) and delay value (default 5s)
can also be set;
9
Over Frequency
(0-200)%
114
Rated frequency percentage; return value
(default 110%) and delay value (default 5s)
can also be set;
10
Under Frequency
(0-200)%
90
Rated frequency percentage; return value
(default 94%) and delay value (default 5s)
can also be set;
11
CT Ratio
(5-6000)/5
500
Ratio of externally connected CT;
12
Full-load
Active
Power
(1-60000)kW
345
Full-load active power of mains, used for
load share;
13
Full-load
Reactive
Power
(1-60000)kvar
258
Full-load reactive power of mains, used for
load share;
14
Sync. Alarm
(0-1)
0
0: Electrical Trip
1: Aux. Mains Fail