HGM6100K Series Automatic Generator Module
HGM6100K Series Automatic Generator Module ISSUE 2011-04-12 Version 1.6 Page 9 of 31
4.3 MANUAL OPERATION
1) HGM6120KC, Auto starts mode is active when press
and its indicator is
illuminating. Press
, then controller under
“Manual Test Mode” and its
indicator is illuminating. Under the both modes, press
to start genset, and
it can automatic detect start successfully and accelerate to Hi-speed running. If
there is Hi-temperature, low oil level and voltage abnormal during diesel genset
running, controller can protect genset to stop quickly (detail procedures please
refer to No.4~9 of Auto start operation). Under
“Manual Test Mode
“,
genset with load is decided by Mains is normal or not. If mains are normal,
loading switch is never transferred; while mains are abnormal, loading switch is
transferred into gens side. Under
“Manual Test Mode
“, after genset runs
well in high speed, no matter mains is normal or not, loading switch must be
transferred into gens side.
2) HGM6110KC, Auto starts mode is active when press
, and its indicator is
illuminating. Then press
to start generator, it can automatic detect start
successfully and genset automatic accelerates to Hi-speed running. If there is
Hi-temperature, low oil level and voltage abnormal during diesel genset running,
controller can protect genset to stop quickly (detail procedures please refer to
No.4~9 of Auto start operation). After genset runs well in High speed, controller
will send signal of gens close.
3) Manual stop, press
can shut down the running genset (detail procedures
please refer to No.3~7 of Auto stop operation).
5 PROTECTION
5.1 WARNING
When controller detects the warning signal, only alarm and not stop genset. The
alarms are displayed in LCD.
Warnings as following,
No.
Type
Description
1
Lost of speed
When controller detected the speed of genset is 0 and
speed lost delay set as 0, controller will send warning
alarm signal and it will be displayed in LCD