12 INSTALLATION
The controller is designed to panel installation mode, and it is fixed by clamps
when it is installed. The overall dimension and panel tapping dimension are given
as follows:
1) Battery voltage input
HGM6100K series controller can be applicable to (8-35)VDC battery voltage
environment, battery anode must be reliable connect engine shell B + and B-
controller power battery anode and cathode connections is not less than 2.5, if
there was the float electrical, please put the charger output wire directly to
battery is negative, and from the battery is connected to the anode separately
on the power input, positive controller to prevent the normal operation of the
controller battery charger interference.
2) Speed sensor input
Speed sensor is installed in the engine block of magnetic device testing
flywheel teeth, it should be used with the controller of attachment 2 core
shielding line, shielding layer on the 16th pin controller, the other end terminal,
the other two are respectively in signal controller, and meet the terminals15th
and 16th pin. At full speed sensor output voltage range should be in 1-24VAC
(RMS), recommend voltage for 12VAC (in the rated speed). When the velocity
sensor can be installed to contact the flywheel spinning sensor first, then pour
out 1/3 laps, finally will lock nut on the sensor.
3) Output and relays
Controller for all output relay contacts output, if need to expand relays, please
will expand relay coil free-wheeling diode (increased ends when extended
relay coil links DC) or increase resistance and capacitance loop (when
extended relay coil links AC), in order to prevent interference controller or