![Smartgen HGM6100K Series Скачать руководство пользователя страница 23](http://html1.mh-extra.com/html/smartgen/hgm6100k-series/hgm6100k-series_operating-manual_1297513023.webp)
HGM6100K Series Automatic Generator Module
HGM6100K Series Automatic Generator Module ISSUE 2011-04-12 Version 1.6 Page 23 of 31
Num
Content
Description
5 Reserved 2
7.5 CONDITIONS OF CRANK SUCCEED (TABLE 5)
Num
Content
0
Magnetic pickup sensor
1
Generator
2
Magnetic pickup Generator
3
Magnetic pickup Oil pressure
4
Gen Oil pressure
5
Gen Magnetic pickup Oil pressure
1) The crank disconnect condition has three kinds, the magnetic pickup sensor
and the generator voltage can be used alone, the oil pressure must be used
with the magnetic pickup sensor and the generator voltage, the purpose is to
make the starter and the engine to disconnect as soon as possible.
2) Magnetic pickup sensor is installed in the engine block number of magnetic
device testing flywheel.
3) When choosing magnetic pickup sensor, ensure engine flywheel teeth setting,
otherwise may appear over speeding shutdown or loss speed shutdown.
4) If the generator is not magnetic pickup sensors, please don't choose
corresponding, otherwise this will occur fail to start or loss of speed alarm and
shutdown.
5) If the generator has no oil pressure sensor, please don't choose
corresponding.
6) If the generator starting conditions has not be selected, the controller will not
measure and display the relative parameters (This can be applied to the pump
set), if not choose magnetic pickup sensor, the speed signal will come from the
generating AC signal.