HGM6100K Series Automatic Generator Module
HGM6100K Series Automatic Generator Module ISSUE 2011-04-12 Version 1.6 Page 17 of 31
Num
Parameter
Range
Default
Description
31
Lose speed
delay
(0-20.0)s
5.0
When speed is zero and
remain for the delay, send
out shutdown alarm. When
the delay is zero, send out
warning alarm.
32
Charge fail volt
(0-30)V
6.0
During
generator
is
running,
when
charge
alternator WL/D+ voltage
is under than this point and
remain for 5 seconds,
generator
will
warning
alarm.
33
Battery over volt (12-40)V
33.0
When generator battery
voltage is over than the
point and hold for 20
seconds,
battery
over
voltage signal is active. It‟s
a warning alarm.
34
Battery
under
volt
(4-30)V
8.0
When generator battery
voltage is under than the
point and hold for 20
seconds, battery under
voltage signal is active. It‟s
a warning alarm.
35
CT rate
(5-6000)/5
500
Current transformer rate
36
Full load current
(5-6000)A
500
Mains or generator set
maximum rated current.
37
Over
current
percentage
(50-130)%
120
When the load current is
over than the point, the
over
current
delay
is
initiated.
38
Over
current
delay
(0-3600)s
1296
When load current is over
than the point and hold
great than the timer, send
out over current signal.
When the delay is zero,
over current is disabled.
39
Open
Fuel
Pump threshold
(0-100)%
25
When the fuel level lower
than the set value and for
10 seconds, the output
signal to open fuel pump.