![Smartgen HGM6100K Series Скачать руководство пользователя страница 20](http://html1.mh-extra.com/html/smartgen/hgm6100k-series/hgm6100k-series_operating-manual_1297513020.webp)
HGM6100K Series Automatic Generator Module
HGM6100K Series Automatic Generator Module ISSUE 2011-04-12 Version 1.6 Page 20 of 31
Num
Content
Description
2
ETS solenoid hold
The designated programmable output relay
will energize when a stop signal has been
activated. The output will remain energized for
pre-set timer once the engine has come to a
complete stop, then de-energizes.
3
Idle control
The designated programmable output relay
will energize when the idle delay is not zero.
The output contact would typically be
connected to the “idle/run” input control of an
electronic governor.
4
Preheat control
The designated programmable output relay
will energize during the preheat delay timer
period and also energize until the engine
receive a crank success signal. The preheat
output is typically used for an engine starting
aid such as glow plugs.
5
Closed Gens
Switch generator breaker on.
6
Closed Mains
Switch mains breaker on.(HGM6120KC)
7
Open ATS
Switch breaker off. The output delay is 3
seconds.
8
Raise speed
In the process of warm-up when he entered
the suction, suck time for high-speed warm-up
delay time. Raise speed auxiliary input
effective disconnect.
9
Drop speed
Enter into stop idling process or to ETS
solenoid stop (when alarm stop) sucked, and
suck time to stop idling delay time. Drop
speed when the auxiliary active disconnect.
10
Generator run output
Outputting when genset in normal running
and disconnected after speed is lower than
start successful speed value.
11
Fuel pump control
When the fuel level lower than the set
threshold to open the fuel pump or input a low
oil level warning enter active pull; when the
fuel level over than that set off the fuel pump
and the input threshold of the low oil level
warning off when input is inactive open.
12
High speed control
Outputting when genset enters into "Warming
Up" and disconnected after "Cooling Down" is
over.
13
System in automatic
mode
The controller work in automatic mode.