![Smartgen HGM6100K Series Скачать руководство пользователя страница 11](http://html1.mh-extra.com/html/smartgen/hgm6100k-series/hgm6100k-series_operating-manual_1297513011.webp)
HGM6100K Series Automatic Generator Module
HGM6100K Series Automatic Generator Module ISSUE 2011-04-12 Version 1.6 Page 11 of 31
No.
Type
Description
alarm
set for alarming, it will send a stop alarm signal and it
will be displayed in LCD
6
Speed
signal
lost alarm
When controller detected genset speed is 0 or delay is
not 0, it will send a stop alarm signal and it will be
displayed in LCD
7
Gens
over
voltage
When controller detected genset voltage is over than
set for alarming, it will send a stop alarm signal and it
will be displayed in LCD
8
Gens
under
voltage
When controller detected genset voltage is under
than set for alarming, it will send a stop alarm signal
and it will be displayed in LCD
9
Gens
over
current
When controller detected genset current is over than
set for alarming or delay is not 0, it will send a stop
alarm signal and it will be displayed in LCD
10
Start
failed
alarm
During the start attempt times, if genset start failed, it
will send a stop alarm signal and it will be displayed in
LCD
11
Over frequency
alarm
When controller detected genset frequency is over than
set for alarming, it will send a stop alarm signal and it
will be displayed in LCD
12
Under
frequency alarm
When controller detected genset frequency is under
than set for alarming, it will send a stop alarm signal
and it will be displayed in LCD
13
Gens
failed
alarm
When controller detected genset frequency is 0, it will
send a stop alarm signal and it will be displayed in LCD
14
Oil level lower
alarm
When controller detected genset oil lever lower input is
active, it will send a stop alarm signal and it will be
displayed in LCD
15
Water
level
lower alarm
When controller detected genset water level lower input
is active, it will send a stop alarm signal and it will be
displayed in LCD
6 Connecting terminal
HGM6110KC compared with HGM6120KC, is less a Mains three phase AC input
terminal. The HGM6110KC and HGM6120KC backplane is as following.