HGM6100K Series Automatic Generator Module
HGM6100K Series Automatic Generator Module ISSUE 2011-04-12 Version 1.6 Page 22 of 31
Num
Content
Description
active and a remote start signal/mains failure
occurs the HGM6110/20K will not give a start
command to the generator. If this input signal is
then removed, the HGM6110/20K will operate
as if a remote start/mains failure has occurred,
starting and loading the generator. This
function can be used to give an
‘AND’
function
so that a generator will only be called to start if
the mains fails and another condition exists
which requires the generator to run. If the
„Auto start Inhibit‟ signals become active once
more it will be ignored until the module has
returned the mains supply on load and
shutdown.
7.4 SENSOR SELECTION (TABLE 4)
Num
Content
Description
1
Temperature
Sensor
0 Not used
1 Defined Res. Type
2 VDO
3 SGH(Huanghe sensor)
4SGD(DongKang sensor)
5 CURTIS
6 DATCON
7 VOLVO-EC
8 SGX
9 Reserved
Defined input resistance
range
is
0~6000
Ω,
factory default is SGX.
2
Pressure
Sensor
0 Not used
1 Defined Res. Type
2 VDO 10Bar
3 SGH(Huanghe sensor)
4 SGD(DongKang sensor)
5 CURTIS
6 DATCON 10Bar
7 VOLVO-EC
8 SGX
9 Reserved
Defined input resistance
range
is
0~6000
Ω,
factory default is SGX.
3
Fuel Level
Sensor
0 Not used
1 Defined Res. Type
2 SGH
3 SGD
4 Reserved 1
Defined
curve
input
resistance
range
is
0-6000
Ω, factory default
is SGD.