HAT553V ATS Controller User Manual Page 25 of 32
NOTE
: this function is only suitable for switches with breakings and switches allowing to transfer directly from A power
loading to B power loading.
10.3
AUXILIARY CONTACT FEEDBACK INPUT OF SWITCH OPEN
If switch needs to access to open feedback input, please firstly set open input enabled. Detailed setting
method: in parameter setting interface enter "switch setting" interface, find "open input enable" and set
it enabled; Then set auxiliary input port 1 "19: Open IN", when auxiliary input 1 detects low electrical
level, open input is active.
During the transfer process, if failed to close of A power occurs, A power switch won't execute close
action, B power is Ok, and B power close is executed. If failed to open occurs, controller won't execute
switch close/open actions.
11
COMMUNICATION CONFIGURATION AND CONNECTION
11.1
ILLUSTRATION
HAT553V dual power transfer controller has RS422 communication port, USB communication port.
Between them RS422 communication port allows to connect LAN of open structure. Communication
port applies Modbus communication protocol, by the running software on PC or data collecting system,
to provide a simple and practical dual power transfer management method of factories,
telecommunication, industries and civil buildings, realizing "remote control, remote measuring, remote
communicating" functions of dual power monitoring.
For detailed information please refer to
HAT553V Communication Protocol
.
Communication Protocol: Modbus-RTU
Communication Parameters
Module Address 1(Range: 1-254)
Baud Rate 9600bps (2400/4800/9600/19200bps)
Data Bit 8 bit
Parity bit None (None, Odd, Even)
Stop bit 2-bits (1 bit or 2 bits)