7.1.2

 

REMOTE COMMUNICATION START/STOP   

Through RS422 port and by using Modbus protocol control, remote start or remote stop commands can 
be issued.   

Remote Stop:

 Disconnect the outputted genset start signal, which is to control genset stop; 

Remote Start

: Control genset start signal output, which is to control genset start;   

7.2

 

AUTO START/STOP 

7.2.1

 

START REQUIREMENTS   

7.2.1.1.1

 

INPUT PORT START 

Set "Remote Start Onload" or "Remote Start Offload" for configurable input ports, and they are cannot be 
set at the same time.   
Remote  Start  Onload:  Genset  start  outputs,  when  generating  is  Ok,  GB  closes;  when  it  is  inactive, 
disconnect genset start output signal;   
Remote  Start  Offload:  Genset  start  outputs,  when  mains  is  Ok,  MB  closes;  when  it  is  inactive, 
disconnect genset start output signal;   

7.2.1.1.2

 

MAINS ABNORMAL START 

When Mains is abnormal, genset start outputs; when generating is Ok, GB closes;   

7.2.2

 

SCHEDULED START 

When  Scheduled  Gen  Start  is  enabled,  user  can  set  scheduled  start  time;  Controller  will  issue  start 
signal when the time is up; when the scheduled start delay time is over  start signal is disconnected. 
Scheduled start can be set to onload or offload.   

Scheduled Start Onload

: genset start outputs, when generating is Ok, GB closes; 

Scheduled Start Offload:

 genset start outputs, when Mains is Ok, MB closes;   

Scheduled Start Cyclical Time can be set to Start Monthly/Weekly/Daily.   

Start Monthly

: Which month to start, start date and time can be set; 

Start Weekly

: Start at the same time of several days in a week can be set; for example, from Monday to 

Friday start at 8:00 every day and last for 10 hours.   

Start Daily

: Start at the same time for each day can be set.   

8

 

PARAMETER CONFIGURATION 

8.1

 

ILLUSTRATION 

In the first page of the main screen, press 

  key to enter menu screen; select "Parameters Set" and 

press  Confirm  key  to  confirm  and  enter  parameter  setting  password  check  interface.  Input  correct 
password and  it will  enter  parameter  main  interface.  If  password  is  wrong, then  it  directly returns  to 

main interface. 

Default password is 

01234

. In parameter setting page, press longer 

  to directly exit 

from this screen and return to main screen.   
 

Содержание HAT553V

Страница 1: ...HAT553V DUAL POWER ATS CONTROLLER USER MANUAL SMARTGEN ZHENGZHOU TECHNOLOGY CO LTD...

Страница 2: ...D START 14 8 PARAMETER CONFIGURATION 14 8 1 ILLUSTRATION 14 8 2 PARAMETER CONFIGURATION TABLE 15 8 3 DIGITAL INPUT OUTPUT FUNCTION DESCRIPTION 18 8 3 1 INPUT PORT FUNCTION DESCRIPTION 18 8 3 2 OUTPUT...

Страница 3: ...HAT553V ATS Controller User Manual Page 3 of 32 12 1 DESCRIPTION OF CONNECTING TERMINALS 27 12 2 TYPICAL WIRING DIAGRAM 29 13 INSTALLATION 31 14 TROUBLESHOOTING 32...

Страница 4: ...including photocopying or storing in any medium by electronic means or other without the written permission of the copyright holder Applications for the copyright holder s written permission to repro...

Страница 5: ...ion Wide working temperature range 40 C 70 C suitable for awful environmental places Collect and display 2 channel 3 phase voltage frequency and phase sequence Display of A power B power accumulated c...

Страница 6: ...AC250V Volts free output Digital Close Input Active when A CLOSE and IN COM short connected Active when B CLOSE and IN COM short connected Forced to Open Input GND IN COM connected is active Digital...

Страница 7: ...er line voltage 3 A B power voltage phase sequence 4 A B power frequency 5 Present continuous supply time 6 Last time continuous supply time 7 A power accumulated supply time 8 B power accumulated sup...

Страница 8: ...current is Auto mode Manual Mode Indicator Light on when current is Manual mode A Power Indicator Always light on when A AC power is normal flashing when it is abnormal light off when it is outage A P...

Страница 9: ...where the cursor is In main screen pressing longer is lamp test when lamp test is done LCD backlight is illuminated LCD displays all dark and all LED indicators on the panel are illuminated NOTE Pres...

Страница 10: ...A Total Supply Time B Total Supply Time A Total Close Nums B Total Close Nums Information Controller model version release date LCD temp display and start interface 6 3 STATUS DESCRIPTION Table 8 A P...

Страница 11: ...rking Genset start signal outputs 5 Genset Standby None genset start signal outputs Table 11 Switch Status No Item Description 1 Ready to Transfer Enter switch transfer procedure 2 Closing A A power i...

Страница 12: ...output 3 B Failed to Close Switch didn t close properly after B power close signal is stopped to output 4 B Failed to Open Switch didn t succeed to close properly after B power open signal is stopped...

Страница 13: ...nterface NOTE Password is needed for entering parameter settings and default password is 01234 Operators can change the password to prevent others changing controller configurations randomly Please re...

Страница 14: ...user can set scheduled start time Controller will issue start signal when the time is up when the scheduled start delay time is over start signal is disconnected Scheduled start can be set to onload o...

Страница 15: ...0 30000 V 220 Rated voltage value for AC system 9 Over Volt Set 0 1 1 0 Disable 1 Enable 10 Over Volt Value 0 200 120 Voltage upper limit abnormal when it is over upper limit 11 Over Volt Return 0 20...

Страница 16: ...open failed then it closes again and close again delay starts when delay is over it opens again if it cannot open then it issues failed to open alarm signal 6 Again Open Delay 0 20 0 s 1 0 For the fir...

Страница 17: ...Week Sunday Monday Tuesday Wednesday Thursday Friday Saturday 7 Schedule Hours 0 23 h 0 Time for scheduled start 8 Schedule Minutes 0 59 min 0 9 Schedule Work Time 0 30000 min 30 Lasting time for sche...

Страница 18: ...art Inhibit Input Inhibit genset start signal output In auto mode after stop delay is over controller disconnects genset start signal output In manual mode if genset is started manual stop is needed a...

Страница 19: ...d B both are abnormal 10 A Available Output when A is normal 11 A Unavailable Output when A is abnormal 12 B Available Output when B is normal 13 B Unavailable Output when B is abnormal 14 Auto Mode O...

Страница 20: ...ne is the newest Users can check each item via Down key When recorded items are over 50 new item will cover the newest record Record type includes Action Event Warn Event Fault Event Fault events are...

Страница 21: ...r Key Icon Key Name Function Description A Power Close Press and if load is in open status A power closes and load is supplied by A power B Power Close Press and if load is in open status B power clos...

Страница 22: ...ESTORE When Auto Trans Restore is set A power is master if A power is normal then A power closes if A power is abnormal B power is normal then A power opens B power closes if A power recovers normal t...

Страница 23: ...re is set and Mutual Backup is active A power is master If A power is normal then A power closes if A power is abnormal B power is normal then A power opens and B power closes If A power recovers norm...

Страница 24: ...E Master power A power close needs to transfer to manual mode and by button operation close otherwise in auto mode switch only transfers between open and backup power B power position 10 2 4 NONE OPEN...

Страница 25: ...f failed to open occurs controller won t execute switch close open actions 11 COMMUNICATION CONFIGURATION AND CONNECTION 11 1 ILLUSTRATION HAT553V dual power transfer controller has RS422 communicatio...

Страница 26: ...NNECTION The HAT553V dual power ATS controller is equipped with RS422 communication port which can be LAN monitored by RS485 device or by RS422 device The communication connection is shown as followin...

Страница 27: ...SB communication port can be used to connect PC test software and configure parameters and at the same time it can be used for module program upgrade Fig 7 USB Connecting Diagram 12 DEFINITION OF CONN...

Страница 28: ...or single phase input only connect BR and BN 11 BS 12 BT 13 BN 14 AR A VOLTAGE INPUT AC 3 Phase 4 Wire voltage input of A power For single phase input only connect AR and AN 15 AS 16 AT 17 AN 18 GENSE...

Страница 29: ...ide power supply for controller 34 B1 DC Power 1 positive input 35 B DC power negative common port USB USB D form USB communication port Configure parameters and upgrade program by connecting with PC...

Страница 30: ...m NOTE The switch type of FEITENG application diagram is set as two breaking Fig 11 Contactor Application Diagram NOTE The switch type of contactor application diagram is set as two breaking the closi...

Страница 31: ...nder Voltage Trip MX Open Relay XF Close Relay NOTE 2 The under voltage trip delay of breaker is not less than 1s NOTE 3 The switch type is set as two breaking 13 INSTALLATION The controller is design...

Страница 32: ...ary output connecting wire pay attention to N O and N C points Check output port setting function and output type in parameter settings Auxiliary Input Abnormal Check whether aux input port is GND con...

Отзывы: