HAT553V ATS Controller User Manual Page 14 of 32
7.1.2
REMOTE COMMUNICATION START/STOP
Through RS422 port and by using Modbus protocol control, remote start or remote stop commands can
be issued.
Remote Stop:
Disconnect the outputted genset start signal, which is to control genset stop;
Remote Start
: Control genset start signal output, which is to control genset start;
7.2
AUTO START/STOP
7.2.1
START REQUIREMENTS
7.2.1.1.1
INPUT PORT START
Set "Remote Start Onload" or "Remote Start Offload" for configurable input ports, and they are cannot be
set at the same time.
Remote Start Onload: Genset start outputs, when generating is Ok, GB closes; when it is inactive,
disconnect genset start output signal;
Remote Start Offload: Genset start outputs, when mains is Ok, MB closes; when it is inactive,
disconnect genset start output signal;
7.2.1.1.2
MAINS ABNORMAL START
When Mains is abnormal, genset start outputs; when generating is Ok, GB closes;
7.2.2
SCHEDULED START
When Scheduled Gen Start is enabled, user can set scheduled start time; Controller will issue start
signal when the time is up; when the scheduled start delay time is over start signal is disconnected.
Scheduled start can be set to onload or offload.
Scheduled Start Onload
: genset start outputs, when generating is Ok, GB closes;
Scheduled Start Offload:
genset start outputs, when Mains is Ok, MB closes;
Scheduled Start Cyclical Time can be set to Start Monthly/Weekly/Daily.
Start Monthly
: Which month to start, start date and time can be set;
Start Weekly
: Start at the same time of several days in a week can be set; for example, from Monday to
Friday start at 8:00 every day and last for 10 hours.
Start Daily
: Start at the same time for each day can be set.
8
PARAMETER CONFIGURATION
8.1
ILLUSTRATION
In the first page of the main screen, press
key to enter menu screen; select "Parameters Set" and
press Confirm key to confirm and enter parameter setting password check interface. Input correct
password and it will enter parameter main interface. If password is wrong, then it directly returns to
main interface.
Default password is
01234
. In parameter setting page, press longer
to directly exit
from this screen and return to main screen.