Table 18 Output Port Function Description
No.
Item
Description
0
Not Used
Invalid
1
Common Alarm
Common alarms include fault alarm, warning alarm.
2
Common Fault Alarm
Fault alarm includes switch transfer failure.
3
Common Warn Alarm
Warning alarms include A phase sequence wrong, B phase
sequence wrong, and forced to open.
4
Transition Fault
Switch transfer failures include A failed to close, A failed to open, B
failed to close, and B failed to open.
5
Audible Alarm
When fault alarms are active, external annunciator can be
connected;
After delay for 60s, clear the audible alarm output.
6
Reserved
7
Reserved
8
Transition Output
Relay outputs when switch close/open transfers; it stops outputting
when transfer is over; shortest output time is 1s.
9
A&B Abnormal
Output when A and B both are abnormal.
10
A Available
Output when A is normal.
11
A Unavailable
Output when A is abnormal.
12
B Available
Output when B is normal.
13
B Unavailable
Output when B is abnormal.
14
Auto Mode
Output when controller is in auto mode.
15
Manual Mode
Output when controller is in manual mode.
16
Genset Start Output
Control genset to start.
17
Breaking Compulsory
Output when Forced to Open is active.
18
A Close Control
Control A switch to close.
19
A Open Control
Control A switch to open.
20
B Open Control
Control B switch to close.
21
B Open Control
Control B switch to open.
22
Open Control
Control A and B switches to open.
23
Reserved
24
Reserved
25
A Closed Input
A switch closed status is outputted when switch is at I position.
26
B Closed Input
B switch closed status is outputted when switch is at II position.
27
Opened Input
Switch open status is outputted when switch is at 0 position and it
needs to enable open input function and configure input to open
input; when this input is active, it outputs.
28
Reserved
29
Reserved
30
Reserved
31