![Smartgen HAT553V Скачать руководство пользователя страница 17](http://html1.mh-extra.com/html/smartgen/hat553v/hat553v_user-manual_1297488017.webp)
HAT553V ATS Controller User Manual Page 17 of 32
No.
Item
Range
Default
Description
when delay is over, controller issues genset
start signal.
2
Genset Stop Delay
(0~9999)s
5
Delay starts when genset prepares to stop;
when delay is over, controller disconnects
genset start signal.
Scheduled Start/Stop Setting
1
Schedule Gen Enable (0~1)
0
0: Disable 1: Enable
2
Schedule Load
(0~1)
0
0: Off Load 1: On Load
3
Schedule Period
(0~2)
0
0: Monthly
1: Weekly
2: Daily
4
Schedule Monthly
Month
January February March
April May June
July August September
October November December
5
Schedule Date
(1~31)
1
Date for genset start for each month.
6
Schedule Weekly
Week
Sunday Monday Tuesday
Wednesday Thursday Friday
Saturday
7
Schedule Hours
(0~23)h
0
Time for scheduled start.
8
Schedule Minutes
(0~59)min
0
9
Schedule Work Time (0~30000)min
30
Lasting time for scheduled start running.
Programmable Input Setting
1
Digital Input 1
(0~20)
0
Not Used
2
Active Type
(0~1)
0
0: Close to Activate 1: Open to Activate
Programmable Output Setting
1
Relay Output 1 Active
Type
(0~1)
0
0: Output(N/O) 1: Output (N/C)
2
Relay Output 1
(0~36)
1
Common Alarm
Module Setting
1
Power On Mode
(0~2)
0
0: Previous Mode
1: Manual Mode
2: Auto Mode
2
Language
(0~1)
0
0: Simplified Chinese 1: English
3
Password
(00000~65535) 01234 Password for entering parameter setting
4
Module Address
(1~254)
1
Communication address for RS485 network
5
Com Baud Rate
(0~3)
2
0: 2400bps
1: 4800bps
2: 9600bps
3: 19200bps
6
Com USART Parity
(0~2)
0
0: None
1: Odd Parity