![Smartgen HAT553V Скачать руководство пользователя страница 11](http://html1.mh-extra.com/html/smartgen/hat553v/hat553v_user-manual_1297488011.webp)
HAT553V ATS Controller User Manual Page 11 of 32
Table 9 B Power Voltage Status
No.
Item
Description
1
B Available
Delay for B power available detection
2
B Unavailable
Delay for B power unavailable detection
3
Power Normal
Power value is within normal range.
4
Blackout
Voltage is 0.
5
Over Volt
Voltage is above the pre-set upper limit.
6
Under Volt
Voltage is less than the pre-set lower limit.
7
Over Frequency
Frequency is above the pre-set upper limit.
8
Low Frequency
Frequency is less than the pre-set lower limit.
9
Loss Phase
One or two phases are lost among L1, L2, L3.
10
Phase Wrong
Phase sequence is wrong for L1-L2-L3.
Table 10 Genset Status
No.
Item
Description
1
Genset Start Delay
Delay time before genset start
2
Genset Stop Delay
Delay time before genset stop
3
Schedule Work
Lasting time for scheduled start is displayed when scheduled start is
active.
4
Genset Working
Genset start signal outputs.
5
Genset Standby
None genset start signal outputs.
Table 11 Switch Status
No.
Item
Description
1
Ready to Transfer
Enter switch transfer procedure
2
Closing A
A power is experiencing close delay.
3
Opening A
A power is experiencing open delay.
4
Closing B
B power is experiencing close delay.
5
Opening B
B power is experiencing open delay.
6
Transfer Rest
The interval time for switch transfer
7
Closing A Again
Again close time when A power failed to open for the first time, if
Again Close Delay is not set to 0.
8
Opening A Again
Again open time when A power failed to close for the first time, if
Again Close Delay is not set to 0.
9
Closing B Again
Again close time when B power failed to open for the first time, if
Again Close Delay is not set to 0.
10
Opening B Again
Again open time when B power failed to close for the first time, if
Again Close Delay is not set to 0.
11
A On Load
A power is closed and A power takes the load.
12
B On Load
B power is closed and B power takes the load.
13
Offload
Switch has been open and load is disconnected.