![Smartgen HAT553V Скачать руководство пользователя страница 10](http://html1.mh-extra.com/html/smartgen/hat553v/hat553v_user-manual_1297488010.webp)
HAT553V ATS Controller User Manual Page 10 of 32
6.2
SECOND LEVEL INTERFACE
Table 7 Second Level Display
Item
Display Contents
Parameter Settings
AC Config.
Switch Config.
Genset Config.
Scheduler Config.
Digit Inputs Config.
Relay Outputs Config.
Module Config.
History Record
Running mode switch event;
Start/stop event;
Fault event;
Auto Trans./Restore
Auto Trans./Restore;
Each Backup;
Test Genset
Manual Start/Stop;
Date and Time Set
Module date and time setting;
Language
Display language setting;
Total Information
Continuous Power Supply Time;
Last Continuous Power Supply;
A Total Supply Time;
B Total Supply Time;
A Total Close Nums;
B Total Close Nums;
Information
Controller model, version, release date, LCD temp. display and start
interface.
6.3
STATUS DESCRIPTION
Table 8 A Power Voltage Status
No.
Item
Description
1
A Available
Delay for A power available detection
2
A Unavailable
Delay for A power unavailable detection
3
Power Normal
Power value is within normal range.
4
Blackout
Voltage is 0.
5
Over Volt
Voltage is above the pre-set upper limit.
6
Under Volt
Voltage is less than the pre-set lower limit.
7
Over Frequency
Frequency is above the pre-set upper limit.
8
Low Frequency
Frequency is less than the pre-set lower limit.
9
Loss Phase
One or two phases are lost among L1, L2, L3.
10
Phase Wrong
Phase sequence is wrong for L1-L2-L3.