APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 46 of 62
7.5 CONDITIONS OF CRANK DINSCONNECT SELECTION
No.
Setting description
0
Oil pressure
1
Engine Speed
2
Oil pr Engine Speed
NOTE:
1. There are 3 conditions to make starter disconnected with engine. Engine speed and
oil pressure both can be used separately. We recommend that oil pressure should
be using with engine speed together, in order to make the starter motor is separated
with engine immediately and can check crank disconnect exactly.
2. Engine speed is the magnetic equipment which be installed in starter for detecting
flywheel teeth.
3. When set as engine speed, must ensure that the number of flywheel teeth is as same
as setting, otherwise, “over speed shutdown” or “under speed shutdown” may be
caused.
4. If pump unit without engine speed sensor
, please don’t select corresponding items,
otherwise, “start fail” or “loss speed signal” maybe caused.
5.
If genset without oil pressure sensor, please don’t select corresponding items.