APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 33 of 62
No.
Items
Parameter
Default
Description
value can be set.
6
Low Warn
(0-9000)%
20
Warn when external sensor value is
lower than this value. The delay
value, “warn enable” and return
value can be set.
7
Custom
Curve
Users should set the corresponding
curve when select resistor curve
type or current curve type.
8
Rated Outlet
Pressure
(0-9000)kPa
1000
Set the outlet port’s rated working
pressure of pump unit.
9
Static
Pressure
(0-9000)kPa
0
Set the out
let port’s static pressure
of pump unit.
10
Flow
Function
(0-1)
0
0: Disable
;
1: Enable
11
Rated Flow
(0-10000)m³/h 1000
Pump unit’s rated working pressure.
12
Over
Flow
Warn
(0-1000)%
110
During normal running process, it
will initiated a warning alarm signal
when flow value has exceed the set
value. The delay value, “warn
enable” and return value can be set.
13
Over
Flow
Shut
(0-1000)%
120
During normal running process, it
will initiate a shutdown alarm signal
when flow value has exceeded the
set value
. The “warn enable” and
delay value can be set.
14
Flow Curve
Different
outlet
pressures
correspond to different flow value.
Flexible Input Ports
Flexible Input Port 1
1
Contents
Setting
(0-53)
28
Remote start (on load). See form 3.
2
Active Type
(0-1)
0
0: Closed to active 1: Open to
active
Flexible Input Port 2
1
Contents
Setting
(0-53)
26
High temperature shutdown.
See form 3.
2
Active Type
(0-1)
0
0: Closed to active 1: Open to
active
Flexible Input Port 3
1
Contents
Setting
(0-53)
27
Low oil pressure shutdown.
See form 3.
2
Active Type
(0-1)
0
0: Closed to active 1: Open to
active