APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 28 of 62
7 DEFINITION AND RANGE OF PARAMETERS
7.1 PARAMETER CONTENTS AND RANGE (TABLE 1)
No.
Items
Parameter
Default
Description
Timer Setting
1
Start Delay
(0-3600)s
1
Time from remote start signal is
active to start the pump unit.
2
Stop Delay
(0-3600)s
1
Time from remote stop signal is
deactivated to stop the pump unit.
3
Preheat
Delay
(0-3600)s
0
Time of pre-powering heat plug
before starter is powered up.
4
Cranking
Time
(3-60)s
8
Time of starter power up
5
Crank Rest
Time
(3-60)s
10
The waiting time before second
power up when engine start fail.
6
Safety
On
Delay
(0-3600)s
10
Alarms for low oil pressure, high
temperature, under speed, under
frequency/voltage, charge fail are
inactive.
7
Start
Idle
Time
(0-3600)s
0
Idle running time of the pump unit
when starting.
8
Warming Up
Time
(0-3600)s
10
Warming time between the pump
unit take load and high speed
running.
9
Cooling
Time
(0-3600)s
10
Radiating time before stop the pump
unit, after it unloads.
10
Stop
Idle
Time
(0-3600)s
0
Idle running time when pump unit
stop.
11
ETS
Solenoid
Hold
(0-3600)s
20
Stop electromagnet’s power on time
when pump unit is stopping.
12
Fail to Stop
Delay
(0-3600)s
0
Time between ending of pump unit
idle delay and stopped when “ETS
time” is set as 0;
Time between ending of ETS hold
delay and stopped when “ETS Hold
output time” is not 0.
13
After
Stop
Time
(0-3600)s
0
Time between pump unit stopped
and standby.
Engine Setting
1
Engine Type (0-39)
0
Default: Conventional genset (not
J1939)
When connected to J1939 engine,