APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 29 of 62
No.
Items
Parameter
Default
Description
choose the corresponding type.
2
Flywheel
Teeth
(10-300)
118
Tooth number of the engine, for
judging
of
starter
separation
conditions and inspecting of engine
speed. See the following Installation
Instruction.
3
Rated Speed (0-6000)RPM
1500
Offer
standard
to
judge
over/under/loading speed.
4
Speed
on
Load
(0-1000)%
90%
Setting value is percentage of rated
speed. Controller detects when it is
ready to load. It won’t enter into
normal running process when speed
is lower than loading speed.
5
Loss
of
Speed
Signal
(0-3600)s
5
Time from detecting speed is 0 to
confirm the action.
6
Loss
of
Speed
Action
(0-1)
0
0:Warn; 1:Shutdown
7
Over Speed
Shutdown
(0-1000)%
114%
Setting value is percentage of rated
speed and delay value can be set.
8
Under
Speed
Shutdown
(0-1000)%
80%
9
Over Speed
Warn
(0-1000)%
110%
Setting value is percentage of rated
speed. Delay value and return value
can be set.
10
Under
Speed Warn
(0-1000)%
86%
11
Battery
1
Rated
Voltage
(0-60.0)V
24.0
Standard for detecting over/under
voltage of battery.
12
Battery
1
Over Volts
(0-1000)%
120%
Setting value is percentage of rated
voltage of battery. Delay value &
return value can be set.
13
Battery
1
Under Volts
(0-1000)%
85%
14
Battery
2
Rated
Voltage
(0-60.0)V
24.0
Standard for detecting over/under
voltage of battery.
15
Battery
2
Over Volts
(0-1000)%
120%
Setting value is percentage of rated
voltage of battery. Delay value &
return value can be set.
16
Battery
2
Under Volts
(0-1000)%
85%
17
Charge
Alt (0-60.0)V
8.0
In normal running, when charger