APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 41 of 62
172
Config 6 High Shut
173
Config 6 Low Shut
174
Outlet High Warn
175
Outlet Low Warn
176
Outlet High Shut
177
Outlet Low Shut
178~229 Reserved
230
Stop Mode
Action in stop mode.
231
Manual Mode
Action in Manual mode.
232
Reserved
233
Auto Mode
Action in Auto mode.
234
Loading Status
Indicate the system is on-load.
235~239 Reserved
7.2.1 Custom Period Output
Defined Period output is composed by 2 parts, period output S1 and condition output S2.
While S1 and S2 are
TRUE
synchronously, OUTPUT;
While S1 or S2 is
FALSE
, NOT OUTPUT.
Period output S1, can set pump unit
’s one or more period output freely, can set the
delayed time and output time after enter into period.
Condition output S2; can set as any conditions in output ports.
NOTE:
when delay time and output time both are 0 in period output S1, it is
TRUE
in
this period.
Example,
Output period: start
Delay output time: 2s
Output time: 3s
Condition output contents: output port 1 is active
Close when condition output active/inactive: close when active (disconnect when
inactive);
Output port 1 active, after en
ter “starts time” and delay 2s, this defined period output is
outputting, after 3s, stop outputting;
Output port 1 inactive, defined output period is not outputting.