APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 56 of 62
12.12 MTU ADEC(SMART MODULE)
It is suitable for MTU engine with ADEC (ECU8) and SMART module.
Terminals of controller ADEC (X1port)
Remark
Fuel relay output
X1 10
X1 Terminal 9 Connected to
negative of battery
Start relay output
X1 34
X1 Terminal 33 Connected to
negative of battery
Terminals of controller SMART (X4 port)
Remark
CAN GND
X4 3
CAN communication shielding
line(connect to controller
’s this
terminal only)
CAN(H)
X4 1
I
mpedance 120Ω connecting
line is recommended.
CAN(L)
X4 2
I
mpedance 120Ω connecting
line is recommended.
Engine type: MTU-ADEC
12.13 MTU ADEC(SAM MODULE)
It is suitable for MTU engine with ADEC (ECU7) and SAM module.
Terminals of controller ADEC (X1port)
Remark
Fuel relay output
X1 43
X1 Terminal 28 Connected to
negative of battery
Start relay output
X1 37
X1 Terminal 22 Connected to
negative of battery
Terminals of controller SAM (X23 port)
Remark
CAN GND
X23 3
CAN communication shielding
line(connect with controller
’s
this terminal only)
CAN(H)
X23 2
I
mpedance 120Ω connecting
line is recommended.
CAN(L)
X23 1
I
mpedance 120Ω connecting
line is recommended.
Engine type: Common J1939