Configuration
3.13
Via Simatic PDM
Using the Device menu, please, choose the "Calibration" option an then, select the
correspondent transducer block. For example, choosing the transducer block 1:
Figure 3.11 - FI303 - Simatic PDM Calibration Lower/Upper
After pressing “ Lower Calibration”, we get a warning.
When the user press "OK", we have a new window that allows him to enter the desired value for the
new calibrated point for the lower current. Write for example 4.0mA in new value:
After entering the desired valve, the generated current is corrected according to the desired value
and the user can make the correction until the right current is reached. For this purposal, the user
needs to inform the generated current:
Pressing OK, we have:
The user can select
Lower or Upper
calibration.
Pressing this key, the
user starts the lower
calibration method.