background image

FI303 - Operation and Maintenance Instruction Manual 

 

3.4 

PARAMETERS 

DESCRIPTION 

transducer block. 

SP_LO_LIM 

The setpoint low limit is the lowhest setpoint operator entry that can  be used for the 
transducer block. 

BACKUP_RESTORE 

This parameter allows to save and to restore data according to factory and user 
calibration procedures. It has the following options: 
    

1

,  "Factory Cal Restore", 

    

2

,  "Last Cal Restore", 

    

3

,  "Default Data Restore", 

    

4

,  "Shut-Down Data Restore", 

  

11

,  "Factory Cal Backup", 

  

12

,  "Last Cal Backup", 

  

14

,  "Shut-Down Data Backup", 

    

0

,  "None". 

 
XD_ERROR 
 
 
XD_ERROR 

 
Indicates the condition of calibration process according to:        
 
{

16

,  "Default value set"}, 

{

22

, "Applied process out of range"}, 

{

26

, "Invalid configuration for request"}, 

{

27

, "Excess correction"}, 

{

28

, "Calibration failed"} 

MAIN_BOARD_SN 

The electronic main board serial number. 

EEPROM_FLAG 

This parameter is used to indicate EEPROM saving process. 
{

0

, “False”} 

{

1

, “True”} 

ORDERING_CODE 

This array of Unsigned 8 bytes contains information about which kind of materials and 
mechanical parts have been used for the device. This is part of the Ordering Code 
information necessary to buy a spare unit. 

 
Table 3.1 - Parameters Description 
 

PROFIBUS to Current Converter Transducer Block - Parameters Table 

 

Relative 

Index 

Parameter Name 

Object 

Type 

Data Type 

Store 

Size 

Access 

Parameter 

usage/Type 

of Transport 

Initial/Default 

Value 

Mandatory/ 

Optional 

Class 

VIEW 

Standard Parameters  

 

 

13 

 

 

 

 

Additional Parameters for Transducer Block 

 

 

 

FINAL_VALUE 

DS-33 

R/w 

C/a 

 

FINAL_VALUE_SCALE 

Array 

Float 

R/w 

C/a 

4 and 20 mA 

 

10 

CAL_POINT_HI 

Float 

R/w 

C/a 

20 

 

11 

CAL_POINT_LO 

Float 

R/w 

C/a 

 

12 

CAL_MIN_SPAN 

Float 

C/a 

 

13 

CONVERTER_SER_NUM 

Unsigned32 

R/w 

C/a 

 

14 

CONVERTER_MAN 

Octet String 

16 

R/w 

C/a 

"" 

 

15 

CONVERTER_MAINT_DATE 

Octet String 

16 

R/w 

C/a 

"" 

 

16 

FEEDBACK_VALUE 

DS-33 

R/w 

C/a 

 

17 

TERMINAL_NUMBER 

Unsigned8 

R/w 

C/a 

 

18 

TAB_ACTUAL_NUMBER 

See explanation about table handling 

 

 

19 

TAB_ENTRY 

See explanation about table handling 

 

 

20 

TAB_MAX_NUMBER 

See explanation about table handling 

 

 

21 

TAB_MIN_NUMBER 

See explanation about table handling 

 

 

22 

TAB_OP_CODE 

See explanation about table handling 

 

 

23 

TAB_STATUS 

See explanation about table handling 

 

 

Содержание FI303

Страница 1: ......

Страница 2: ...web www smar com contactus asp www smar com Specifications and information are subject to change without notice Up to date address information is available on our website smar...

Страница 3: ...costs Some of the advantages of bi directional digital communications are known from existing smart transmitter protocols Higher accuracy multi variable access remote configuration and diagnostics an...

Страница 4: ...el are allowed to participate in the activities of mounting electrical connection startup and maintenance of the equipment Qualified personnel are understood to be the persons familiar with the mounti...

Страница 5: ...ENT CONVERTER TRANSDUCER BLOCK PARAMETERS TABLE 3 4 CYCLIC CONFIGURATION 3 5 HOW TO CONFIGURE THE ANALOG OUTPUT BLOCK 3 9 CURRENT TRIM 3 12 VIA LOCAL ADJUSTMENT 3 16 TRANSDUCER DISPLAY CONFIGURATION 3...

Страница 6: ...FI303 Operation and Maintenance Instruction Manual VI...

Страница 7: ...ls of the output current Fieldbus 4 a 20 mA Start No Yes Is the indication correct See section 4 Maintenance OK Install the converter on the field following the instructions below Check the area class...

Страница 8: ...FI303 Operation and Maintenance Instruction Manual VIII...

Страница 9: ...cuit is protected by a humidity proof coating but frequent exposures to humidity may affect the protection provided It is also important to keep the covers tightened in place Every time they are remov...

Страница 10: ...rminals one inside the cover and two externals located close to the conduit entries The FI303 uses the 31 25 kbit s voltage mode option for the physical signaling All other devices on the same bus mus...

Страница 11: ...to the certification or specific standard for installation limitations Figure 1 4 Output Connections Avoid routing signal wiring close to power cables or switching equipment The FI303 is protected aga...

Страница 12: ...ength A spur may connect more than one device depending on the length Active couplers may be used to extend spur length The total cable length including spurs between any two devices in the Fieldbus s...

Страница 13: ...the Jumpers J1 This jumper enables the simulation mode parameter in the AO block W1 This jumper enables the local adjustment programming tree Table 1 1 Description of the Jumpers Power Supply The FI3...

Страница 14: ...FI303 Operation and Maintenance Instruction Manual 1 6...

Страница 15: ...ration of block execution self diagnostics and communication The program is stored in PROM For temporary storage of data there is a RAM The data in the RAM is lost if the power is switched off however...

Страница 16: ...on and Maintenance Instruction Manual 2 2 Local Adjustment Two switches that are magnetically activated They can be activated by the magnetic tool without mechanical or electrical contact Figure 2 2 L...

Страница 17: ...u Device option to configure the required parameters using the related menus NOTE It is not advisable to use the Download to Device option This function can misconfigure the equipment How to Configure...

Страница 18: ...he final control element in units of OUT_SCALE Status BAD will indicate a hardware problem FINAL_VALUE_SCALE This is the output conversion of the linearisated value using the high and low scale The en...

Страница 19: ...common to provide a plausibility check in the device The result of this check is indicated in the TAB_STATUS parameter 0 not initialised 1 good new table is valid 2 not monotonous increasing old tabl...

Страница 20: ...for the device This is part of the Ordering Code information necessary to buy a spare unit Table 3 1 Parameters Description PROFIBUS to Current Converter Transducer Block Parameters Table Relative In...

Страница 21: ...cyclic data exchange The FI303 has 3 functional blocks with analog output AOs that the class 1 master uses to execute the cyclic services and the user must choose what configuration best suits their a...

Страница 22: ...de when detecting a communication loss between the slave and the master equipment Since the FI303 will be on a final element it is recommended that a fail safe value be configured The Simatic PDM Proc...

Страница 23: ...ER TAB_MAX_NUMBER TAB_OP_CODE TAB_STATUS The TAB_X_Y_VALUE parameter contains the value couple of the each table entries The TAB_INDEX parameter identifies which element of the table is in the TAB_X_...

Страница 24: ...is is useful for example when the FI303 is controlling a valve with a non linear characteristic Characterization curve when used is applied to the input signal before it is converted by the transducer...

Страница 25: ...The Analog Output Block is a function block used by devices that work as output elements in a control loop like valves actuators positioners etc The AO block receives a signal from another function b...

Страница 26: ...ion Selecting the page Scale Units the user has the option to configure the scale and unit for the input and output Figure 3 7 FI303 Simatic PDM Analog Output Block Scale Units Offline Configuration T...

Страница 27: ...Offline Configuration In terms of Online configuration the user can select at the device menu the Online Configuration for each Analog Output block Figure 3 9 FI303 Simatic PDM Online Configuration mo...

Страница 28: ...t The user can check the calibration of the transducer output by measuring the actual current in the output and compare it with the device s indication of course an appropriate meter should be used If...

Страница 29: ...e have a new window that allows him to enter the desired value for the new calibrated point for the lower current Write for example 4 0mA in new value After entering the desired valve the generated cu...

Страница 30: ...ated current is correct press No and a new warning appears After user confirmation the converter comes to the normal operation The upper calibration procedure is similar than the lower Figure 3 12 FI3...

Страница 31: ...r example 20 0mA in new value After entering the desired valve the generated current is corrected according to the desired value and the user can make the correction until the right current is reached...

Страница 32: ...ce it in orifice S Remove and reinsert the magnetic tool in S until the message Loc Adj is displayed The message will be displayed during approximately 5 sec after the user removes the magnetic tool f...

Страница 33: ...lt Value Set 22 Out of range 26 Invalid Calibration request 27 Excessive Correction Transducer Display Configuration Using the Simatic PDM or any other configuration tool is possible to configure the...

Страница 34: ...the magnetic tool it is necessary to previously prepare the parameters related with this operation via System Configuration There are six groups of parameters which may be pre configured by the user i...

Страница 35: ...Configuration The Local Address Change window allows the user to enable disable the access to change the equipment address Figure 3 15 Parameters for Local Address Configuration When the user enter i...

Страница 36: ...parameters at the same time it is only necessary to opt for none when configure the LCD II Figure 3 16 Parameters for Local Adjustment Configuration The user may select the Mode Block parameter on the...

Страница 37: ...ics screw driver in span hole 4 Wait 3 seconds then MD will appear on display Browse Insert magnetic screw driver in zero hole and hold Select Insert magnetic screw driver in span hole and hold 1 HOW...

Страница 38: ...ocedures Manual Please take a detailed look at this manual in the chapter related to Programming Using Local Adjustment It is significantly the resources on this transducer display also all the Series...

Страница 39: ...justment Fig 3 19 J1 and W1 Jumpers Example let s say we want to calibrate the lower and upper current value From normal display enter local adjustment The display will show Figure 3 20 Step 1 FI303 M...

Страница 40: ...ool in orifice S as soon as lower is shown on the display An arrow pointing upward increment the value and an arrow pointing downward decrement the value Apply the 4 00 mA current in the 1 and 4 termi...

Страница 41: ...tion To implement the correction read the current measured on the Miliamperimeter and use the screwdriver to adjust the figure on the display to this value This option corrects the value of a lower ca...

Страница 42: ...FI303 Operation and Maintenance Instruction Manual 3 26...

Страница 43: ...he FI303 Fieldbus terminals must be between 9 and 32 VDC Electronics Circuit Failure Check circuit boards for defect by replacing them with spare ones NO COMMUNICATION Network Connection Check network...

Страница 44: ...e factory Init use two magnetic screwdrivers Remove the screw on the equipment that fixes the identification tag on the carcass top to access the orifices bearing the letters S and Z The operations to...

Страница 45: ...Reassembly Procedure Put output board 7 into housing 9 Anchor output board with its screws 6 Place the main plate 5 on the carcass and make sure the pins are connected Put display 4 into the housing...

Страница 46: ...justment Protection Cap 10 204 0114 Identification Plate Fixing Screw 11 204 0116 Terminal Insulator 12 314 0123 External Ground Screw 13 204 0124 Housing in Aluminum 14 304 0119 Terminal Holding Scre...

Страница 47: ...ation 185 F without damage Humidity Limits 0 to 100 RH Turn on Time Approximately 10 seconds Update Time Approximately 0 5 second Configuration Basic configuration may be done using local adjustment m...

Страница 48: ...CONVERTER C D Local Indicator 0 1 Without Indicator With Digital Indicator C D Mounting Bracket for 2 Pipe Mounting 0 1 2 Without Bracket Carbon Steel Bracket 316 SST Bracket C D Electrical Connectio...

Страница 49: ...DANCE TO APPROVAL LISTING 3 ASSOCIATED APPARATUS GROUND BUS TO BE INSULATED FROM PANELS AND MOUNTING ENCLOSURES 4 ASSOCIATED APPARATUS GROUND BUS RESISTANCE TO EARTH MUST BE SMALLER THAN 1 ONE OHM IF...

Страница 50: ...FI303 Operation and Maintenance Manual 5 4...

Страница 51: ...nterference presents in the area Without interference Temperature Vibration Others ______________________________ Ambient Temperature From __________ C up to __________ C OCCURRENCE DESCRIPTION ______...

Страница 52: ...serial number and dispatch it to our factory For easier analysis and faster solution of the problem the returned material should include the documentation with a description of the failure observed i...

Страница 53: ...operational limits temperature humidity etc according to the instructions manual In addition this Warranty Certificate excludes expenses with transportation freight insurance all of which are the cust...

Страница 54: ...and SMAR and its dealer reserve themselves the right to refuse the service in cases not compliant to those conditions It is the customer s responsibility to tell SMAR and its dealer when the product w...

Отзывы: