SMA Solar Technology AG
Installation Guide
SB50US-80US-IUS094030
83
dFac-MAX*
Hz/s
0.005 ... 4
0.5 (for
country setting
USA/
UL1741/
2005)
Installer
Maximum “rate of frequency
change” before anti-islanding
protection engages
E_Total
kWh
0 ... 200000
0
Installer
Total energy yield of the inverter.
Changing the value can be
necessary when a Sunny Boy is
exchanged and you wish to match
the previously acquired data.
Fac-delta–*
Hz
0.2 ... 3
0.69 (for
country setting
USA/
UL1741/
2005)
Installer
Maximum allowable operating
frequency above and below 60 Hz
Default value is optimal for
installations < 30 kW.
Fac-delta+*
Hz
0 ... 4.5
0.49 (for
country setting
USA/
UL1741/
2005)
Installer
Fac-MinTripTime*
s
0.16 ... 300
0.16
Installer
Utility interconnection frequency trip
time. Default value is optimal for
installations < 30 kW.
Fan-Test
1 / 0
0
Installer
By setting this parameter to "1" you
can check the function of the fans.
This test turns the fans at maximum
speed.
h_Total
h
0 ... 200000
0
Installer
Total operating hours of the inverter.
Changing the value can be
necessary when a Sunny Boy is
exchanged and you wish to match
the previously acquired data.
Memory Function
no function, Default
param., Reset
Op.Data, Reset
errors
no function
Installer
Default param.: Sets all parameters
to default.
Reset Op.Data: Sets all parameters
that are visible in user level to
default values.
Reset errors: Resets all permanent
device disable errors.
Operating Mode
MPP-Operation,
Turbine, V-const,
Stop
MPP
Installer
Operating Modes of the Sunny Boy:
MPP-Operation: Sets the Sunny Boy
in Maximum Power Point Tracking
Mode
V-const: Constant Voltage Mode
(Setpoint defined in “Vconst-Setval“)
Turbine: Operating mode for wind
power plants
Stop: Disconnection from utility, no
operation
T-Max-Fan
°C
0 ... 100
90
Installer
Temperature for maximum fan
rotation speed.
Name
Unit
Range
Default
Password
Level
Description
Содержание SUNNY BOY 8000-US
Страница 2: ......
Страница 10: ...SMA Solar Technology AG 10 SB50US 80US IUS094030 Installation Guide...
Страница 29: ...SMA Solar Technology AG Installation Guide SB50US 80US IUS094030 29 Dimensions of the Wall Mounting Bracket...
Страница 105: ...SMA Solar Technology AG Installation Guide SB50US 80US IUS094030 105...
Страница 106: ...SMA Solar Technology AG 106 SB50US 80US IUS094030 Installation Guide...
Страница 107: ......
Страница 108: ...4 NFSJDB ODPSQPSBUFE XXX TNB BNFSJDB DPN...