![SMA Sunny Boy 6000 Скачать руководство пользователя страница 45](http://html1.mh-extra.com/html/sma/sunny-boy-6000/sunny-boy-6000_installation-manual_1294483045.webp)
Wiring the SB6000U
Wiring the DC Input
SB6000U-13:SE2506
SMA America
5-13
Use the following procedure to connect the DC wires to the
SB6000U
:
1. Verify that the AC breaker is OFF.
2. Verify that the DC disconnect is open in the DC disconnect enclosure.
3. Install a
3/4
-inch conduit fitting in the
SB6000U
’s DC wiring knockout. The DC
knockout is the one farthest to the left on the bottom of the
SB6000U
, as shown in
Figure 5-1 and Figure 5-10. Fasten the conduit fitting on the inside of the
SB6000U
with the appropriate locknut.
4. Install
3/4
-inch conduit between the DC disconnect enclosure and the
SB6000U
’s
DC wiring knockout.
Note:
Refer to Figure 5-10 for steps 5 through 7.
Figure 5-10 DC Connection Terminals
Check both the polarity
and the open-circuit
voltage from the PV strings!
Negative DC
wire connected
to DC- terminal
Positive DC
wire connected
to DC+ terminal