Wiring the SB6000U
5-2
SMA America
SB6000U-13:SE2506
To disconnect the SB6000U, first turn OFF all AC disconnects and then all DC
disconnects. The AC system should always be disconnected before the DC system. After
the SB6000U is de-energized, disconnect the wiring in the reverse order from above.
WARNING: Always wait a minimum of 5 minutes for
stored potentials in the SB6000U to discharge completely
before opening the enclosure.
WARNING: All electrical installations must be done in
accordance with all local electrical codes and the National
Electrical Code (NEC), ANSI/NFPA 70.
WARNING: Before connecting the Sunny Boy 6000U to
the electrical utility grid, contact the local utility company.
This connection must be made only by qualified personnel.
The DC input from the PV array (via the DC disconnect enclosure)
and the output to the AC utility grid connect to the inverter inside the SB6000U’s case.
The internal AC and DC wiring terminals accept a maximum wire size of #6 AWG.
Knockouts are provided on the bottom of the SB6000U near each of the terminals for
the wires to enter the case, see Figure 5-1.
Figure 5-1 Bottom View of the Sunny Boy 6000U Showing 3/4” Wiring Knockouts
3/4” DC Knockout
GFDI Fuse
Communication Cable
Gland
3/4” AC Knockout
http://www.wholesalesolar.com/inverters.html
http://www.wholesalesolar.com/inverters.html
Содержание Sunny Boy 6000
Страница 2: ...http www wholesalesolar com inverters html http www wholesalesolar com inverters html ...
Страница 89: ...http www wholesalesolar com inverters html http www wholesalesolar com inverters html ...
Страница 90: ...http www wholesalesolar com inverters html http www wholesalesolar com inverters html ...