![SMA Sunny Boy 6000 Скачать руководство пользователя страница 53](http://html1.mh-extra.com/html/sma/sunny-boy-6000/sunny-boy-6000_installation-manual_1294483053.webp)
Commissioning
SB6000U-13:SE2506
SMA America
6-1
Section 6:
Commissioning
WARNING: Follow the steps in the commissioning pro-
cedure in the order they are presented. Deviating from
these procedures could expose you to lethal voltages that
can cause serious injury and/or death.
WARNING: Never insert the GFDI fuse into the SB6000U
without the fuse holder base. Latent voltage may still be
present and electric shock may result.
CAUTION: Follow the steps in the commissioning pro-
cedure in the order they are presented. Deviating from these
procedures could cause irreversible damage to the
SB6000U and void the warranty.
All Sunny Boy inverters have a sophisticated system for detecting and responding to PV
array ground faults as required by NEC Section 690.5. The PV array normally operates
in a grounded configuration. The array’s negative conductor is connected to the
grounding system inside the inverter as a part of the UL1741 Listed ground-fault
detection system. The GFDI protection is active whenever there is sufficient DC voltage
to turn on the LCD in the SB6000U.
To commission the SB6000U, follow these simple instructions:
1) Connect the grid voltage to the SB6000U by switching on the main AC circuit breaker
in the main utility panel.
2) Making sure any covering placed over the PV array is removed, switch the DC
disconnect to the on position. If there is sufficient sunlight available, the SB6000U will
enter the “Wait” mode at this time and the green LED will begin to blink.
3) If no AC faults are detected, the “Wait” mode will end after 10 seconds and the green
LED will stop blinking, remain on and the SB6000U will begin to operate normally.
Note:
If there is a ground fault in the array, the
“EarthCurrentMax” error message will be displayed and the
GFDI fuse may clear. If this error message is encountered, switch
off the DC and AC disconnects to the SB6000U and
troubleshoot the array.
http://www.wholesalesolar.com/inverters.html
http://www.wholesalesolar.com/inverters.html
Содержание Sunny Boy 6000
Страница 2: ...http www wholesalesolar com inverters html http www wholesalesolar com inverters html ...
Страница 89: ...http www wholesalesolar com inverters html http www wholesalesolar com inverters html ...
Страница 90: ...http www wholesalesolar com inverters html http www wholesalesolar com inverters html ...