10 Disconnecting the Inverter from Voltage Sources
Prior to performing any work on the inverter, always disconnect it from all voltage sources as
described in this section. Always adhere to the prescribed sequence.
Destruction of the measuring device due to overvoltage
• Only use measuring devices with a DC input voltage range of 1000 V or higher.
Procedure:
1. Disconnect the circuit breaker from all three line conductors and secure against reconnection.
2. Remove the ESS.
3. Loosen two screws of the protective cover using an Allen key (AF 5) and remove the protective
cover.
4. Use a current clamp to ensure that no current is present in the DC cables.
5. Release and remove all DC connectors. To do
this, insert a flat-blade screwdriver or an angled
screwdriver (blade width: 3.5 mm) into one of
the side slots and pull the DC connectors straight
out. Do not pull on the cable.
6.
Danger to life due to high voltages
The capacitors in the inverter take five minutes to discharge.
• Wait five minutes before opening the enclosure lid.
7. Ensure that no voltage is present at the DC inputs of the inverter.
8. Unscrew all the screws of the enclosure lid using an Allen key (AF 5) and remove the
enclosure lid.
9. Use an appropriate measuring device to ensure that no voltage is present at the AC
connecting terminal plate between
L1
and
N
,
L2
and
N
, and
L3
and
N
. Insert the test probe
into each round opening of the terminal.
10 Disconnecting the Inverter from Voltage Sources
SMA Solar Technology AG
Operating Manual
57
STP5-12TL-20-BE-en-15