• Select the parameter
Minimum On power for MFR battery bank
or
Mlt.BatCha.Pwr
and set the desired value. This will configure the power threshold from
which the battery is to be charged.
• Select the parameter
Minimum time before reconnection of MFR battery bank
or
Mlt.BatCha.Tmm
and set the desired value. This will configure the minimum time which
must elapse after charging the battery before the battery can be charged again.
8.9
Setting SMA OptiTrac Global Peak
For partially shaded PV modules, you should set the interval at which the inverter is to optimize the
MPP of the PV system. If you do not want to use SMA OptiTrac Global Peak feature, you can
deactivate the feature.
The basic procedure for changing operating parameters is explained in another section (see
Section 8.5 "Changing Operating Parameters", page 49).
Procedure:
• Select the parameter
Cycle time of the OptiTrac Global Peak algorithm
or
MPPShdw.CycTms
and set the required time interval. The ideal time interval is usually six
minutes. This value should only be increased if the shading situation changes extremely slowly.
☑ The inverter optimizes the MPP of the PV system at the predetermined time interval.
• In order to deactivate the SMA OptiTrac Global Peak feature, select the parameter
OptiTrac
Global Peak switched on
or set
MPPShdw.IsOn
to
Off
.
8 Configuration
SMA Solar Technology AG
Operating Manual
STP5-12TL-20-BE-en-15
52