PARAMETERS - 03 Cooling Pump

No.

Name/Value

Description

0301

PUMP TYPE

Defi nes the cooling pump type

NONE

No cooling pump is connected

D-OUT 4 BLUE HARNESS 

(default)

Cooling pump is connected to Digital Output 4 on the blue harness. See also DIGITAL OUTPUTS parameter 

for more information

HYDRAULIC GREY 

HARNESS

Hydraulic cooling pump on the grey harness

ELECTRIC ECI 

Electric ECI cooling pump

CC MODULE

Cooling Control Module

The CC Module is an external enclosed unit that controls one AC pump and one DC pump. The AC pump is 

prioritized when AC power-pack is running, in other operating states the 24V DC pump is prioritized. If one 

pump fails, the system will try to use the second pump.

0302

PUMP MODE

Defi nes how the cooling pump are operated

DEACTIVATED

Cooling pump will not be activated (used if cooling is provided by external system)

ALWAYS ON

Cooling pump is activated and always running

TEMP CONTROLLED 

(default)

Cooling pump is activated at 45°C (113°F) and deactivated at 40°C (104°F) if system use temperature 

sensor. If system use temperature switches, cooling is controlled by switch state.

0303

ECI PUMP SPEED

Sets ELECTRIC ECI pump speed if selected as PUMP TYPE

800rpm – 1600rpm 

(default 1400rpm)

Speed in steps of 100rpm.

0304

POWER SAVE

Cooling pump power save function.

DEACTIVATED

POWER SAVE is deactivated and cooling pump will act accordingly to PUMP MODE setting (parameter 

0302).

ACTIVATED (default)

Cooling pump will go into power save mode and stop cooling pump and set selected output to 0V when 

there is no system pressure and power-pack is inactive (VFD not running) for more than 10 seconds.

When power save mode is not triggered the cooling pump will act accordingly to PUMP MODE setting 

(parameter 0302).

0305

ECI TRIM FUNCTION

ECI Cooling pump trim function.

Cooling pump trim function is to run the cooling pump for 30 on regular basis to reduce the risk of corrosion, 

growing and sticking seal.

DEACTIVATED

ECI Cooling pump trim function is deactivated

ACTIVATED (default)

Cooling pump starts:

• 

60 seconds after PHC-3 has been powered

• 

every time system- or stabilizer-pressure is applied

• 

every 6 days if PHC-3 has continuous power

0380

ECI FIRMWARE

Shows the ECI cooling pump fi rmware version. This is read only

VERSION 1.5.0

The Version number is requested from the ECI pump

NA

Not Available, ECI pump is not connected

0381

CCM FIRMWARE

Shows the CCM cooling module fi rmware version. This is read only

VERSION 1.00

Version number is requested from the CC Module

NA

Not Available, CC Module is not connected

Menu - Parameters

MC_0201

4.3

PARAMETERS - 05 Digital Outputs

No.

Name/Value

Description

0501 

0502 

0503 

0504 

0505 

0506

D-OUTPUT 1 

D-OUTPUT 2 

D-OUTPUT 3 

D-OUTPUT 4 

D-OUTPUT 5 

D-OUTPUT 6

Sets a function for the selected digital output. Any function can be set to any digital output.

If the number in front of the value/function name is negative (like -1 BOW CROSSOVER) then the output is 

inverted.

0-NOT IN USE (default)

Output is not in use and set to 0V

-1/1-BOW CROSSOVER

Output is activated when input thrust from bow joystick is more than 5%. Remember to set RAMP 

DECREASE time to preferred 3000ms at parameter 2005.

This function is automatically set to D-OUTPUT 1 when parameter 2007 is set to DO-1 BOW CROSSOVER.

-2/2-STERN CROSSOVER

Output is activated when input thrust from stern joystick is more than 5%. Remember to set RAMP 

DECREASE time to preferred 3000ms at parameter 2105.

This function is automatically set to D-OUTPUT 2 when parameter 2107 is set to DO-2 STERN CROSSOVER.

-3/3-COOLING PUMP

Output is activated according to parameter 0302 PUMP MODE

This function is automatically set to D-OUTPUT 4 when parameter 0301 is set to D-OUT 4 BLUE HARNESS.

-4/4- BOW THRUST ACTIVE Output is activated when bow thruster is running.

-5/5-STERN THRUST 

ACTIVE

Output is activated when stern thruster is running.

-6/6-ANY THRUST ACTIVE

Output is activated when bow or stern thruster is running.

-7/7-THRUSTER ENABLED

Output is activated when any joystick panel is ON. This requires PHC-3 FW V1.009 and PJC222/221 FW 

V2.024 or newer

-8/8-STAB.PTO P.UNLOAD

Output is activated when stabilizer is running from PTO pressure.

This function is used on nonstandard option systems (10 4450B-W-X02).

Enabling this function also require setting of parameter 1011-PTO ENGINE INSTANCE.

-9/9-LOW OIL LEVEL 

ALARM

Output is active when there is a low oil level fault

-10/10-BOW CROSSOVER 

WITH BREAK

10-NO Valve: Output is Low (0V) when PVG feed is ON and input thrust from bow joystick is less than 5%. 

Rest of the time the output is High (+24V).

-10-NC Valve: Output is High (+24V) when PVG feed is ON and input thrust from bow joystick is less than 

5%. Rest of the time the output is Low (0V).

Remember to set RAMP DECREASE time to preferred 3000ms at parameter 2005.

-11/11-STERN CROSSOVER 

WITH BREAK

11-NO Valve: Output is Low (0V) when PVG feed is ON and input thrust from bow joystick is less than 5%. 

Rest of the time the output is High (+24V).

-11-NC Valve: Output is High (+24V) when PVG feed is ON and input thrust from bow joystick is less than 

5%. Rest of the time the output is Low (0V).

Remember to set RAMP DECREASE time to preferred 3000ms at parameter 2105.

Menu - Parameters

MC_0201

4.4

Содержание PHC-3

Страница 1: ...d Norway www sleipnergroup com DOCUMENT ID REVISION DATE LANGUAGE To download your language go to www sleipnergroup com Including Installation For Hydraulic Proportional Controller PHC 3 5267 15 K e e...

Страница 2: ...Menu Parameters 6 12 Menu Diagnostic 13 16 Menu Operation 17 18 PHC 3 Alarm Descriptions 19 21 Installation Manual Responsibility of the Installer 22 Considerations and Precautions for S Link Systems...

Страница 3: ...display and button interface allow for local con guration of parameters and info LED Status Hydraulic cooling pump output Stabilizer hydraulics connections dump unload PTO main valve Power 24V Power...

Страница 4: ...or run enable signal from power management system OIL TEMP Oil temp and oil level screen will not show if tank monitor sensor type parameter 0201 is deactivated Tank monitor sensor type set to analogu...

Страница 5: ...ive Faults Menu Device INFO MC_0201 MC_0201 FAULTS flashing in upper left corner when any fault has been triggered Go to ACTIVE FAULTS menu for fault details Menu Active Faults Menu Device INFO Device...

Страница 6: ...ad sharing between two PTO pumps by shutting down the second PTO pump PUMP2 OUTPUT when not needed two PTO pumps control valves required to reduce heat generation in the system and save fuel energy Wh...

Страница 7: ...nalog temp sensor NTC 10K part no 10 2543 0202 OIL ALARM LEVEL Sets the oil alarm level 0 100 default 65 Alarm level in steps of 5 0203 TANK HEIGHT The height of the oil tank If tank don t have flat b...

Страница 8: ...PUMP TYPE 800rpm 1600rpm default 1400rpm Speed in steps of 100rpm 0304 POWER SAVE Cooling pump power save function DEACTIVATED POWER SAVE is deactivated and cooling pump will act accordingly to PUMP M...

Страница 9: ...ning 5 5 STERN THRUST ACTIVE Output is activated when stern thruster is running 6 6 ANY THRUST ACTIVE Output is activated when bow or stern thruster is running 7 7 THRUSTER ENABLED Output is activated...

Страница 10: ...nputs is active and all inputs must be deactivated to deactivate the function 0 NOT IN USE default Digital input is not in use and deactivated 1 1 START POWERPACK When the input is activated the AC po...

Страница 11: ...steps of 1 1009 PTO PUMP PRESSURE DETECT LEVEL De nes detection level for PTO standby pressure if parameter 0104 SYSTEM PRESSURE is set to ANALOG INPUT Pressure above level indicates that main engine...

Страница 12: ...he BOW valve output direction for all parameter 0102 THRUSTER CONFIG settings NORMAL default Normal thruster direction SWAPPED Swapped thruster direction 2003 MAX SPOOL TRAVEL Scaling of valves spool...

Страница 13: ...00ms default 200ms In steps of 100ms 2105 RAMP DECREASE De nes the time the output signal uses to go from 100 to 0 100ms 10000ms default 200ms In steps of 100ms 2106 DIRECTION LOCK De nes the time fro...

Страница 14: ...Pressure 4 Set MAX SPOOL TRAVEL parameter 2003 to what Output in shows at maximum thrust and maximum Sys Pressure Shows live update of inputs and outputs related to stern thruster function In Display...

Страница 15: ...0 Volt 1 output is energized When an output is highlighted the output will be toggled as long as the Enter button is being pushed and held In Display Description LS Dump LS Dump Valve Pump 2 Shutdown...

Страница 16: ...A 0bar STAB PRESSURE Stabilizer Pressure in mA 4 0mA 0bar Shows live update of digital inputs 0 input is shorted to 0 Volt activated 1 input is open deactivated Scroll down to view more inputs In Disp...

Страница 17: ...during reception increments the value After every successful reception the value is decremented Tx Error Count Transmit error counter Error during transmit increments the value After every successful...

Страница 18: ...is displayed While VFD is running it is possible to press Back and go to parameters and change parameter values like 1003 PRESSURE SETPOINT or view DIGITAL OUTPUTS Waiting for power management system...

Страница 19: ...DC current 3 1A ECI cooling pump motor peak current 12 4A Hydraulic cooling pump is selected in parameter 0301 and is ready to be operated The following data is shown in this example Hydraulic oil tem...

Страница 20: ...ircuit System pressure sensor open circuit Sensor not connected or wire break Verify system pressure parameter 0104 10503 0 16 PHC System Pressure Short Circuit System pressure sensor short circuit Wi...

Страница 21: ...ECI cooling pump overvoltage voltage higher than 33 0V Check PHC 3 input voltage is below 33 0V Replace ECI cooling pump 10524 0 54 PHC ECI Cooling Pump Undervoltage ECI cooling pump under voltage vo...

Страница 22: ...MC_0105 The installer must read this document to ensure necessary familiarity with the product before installation Instructions in this document cannot be guaranteed to comply with all international a...

Страница 23: ...system and attach using 4 M5x16 screws 2 Attach the required cables to the PHC 3 MC_0431 MG_0485 1 2 Tank sensor cable Black X3 S Link cable X5 Power colling pump cable Blue X1 Hydraulic colling pump...

Страница 24: ...esigned by olekr Copyright All rights reserved SLEIPNER MOTO 120 217 56 Supply Voltage 9 31 VDC Power consumption Less than 1 0 Watt in stand by Digital output 1 to 6 Max load 2 0 Amp pr output Digita...

Страница 25: ...eally be connected around the middle of the BACKBONE Cable to ensure an equal voltage drop at each end of the BACKBONE Cable The yellow and black wire in the POWER Cable shall be connected to GND and...

Страница 26: ...STB SCU GW 1 Panel TP 43A S link Encoder Encoder 1 4 2 SCU Power Supply cable 3 Encoder cable 5 Encoder cable 5 FCU Harness 6 FCU Harness 6 SCU FCU cable 7 SCU FCU cable 7 VFD BUS cable 8 Pump Power...

Страница 27: ...C 3 X1 Harness Part 151470 1 10 Pump power cable Part 10 2371 24v Pump power cable Part 10 2357 hyd MC_0218 IMPORTANT If installing S link products DO NOT connect any other control equipment to the S...

Страница 28: ...rial number ie Thruster AMS PPC etc Bow Bow STB Stern Stern STB Fill in the type location and serial numbers of the S link devices installed Keeping this as a reference will make the setup procedure e...

Страница 29: ...to the Purchaser at the Warrantor s expense If on the other hand the claim is determined to result from circumstances such as described in section 4 above or a result of wear and tear exceeding that...

Страница 30: ...30 5267 15 2022 PHC 3 MC_0037 Notes...

Страница 31: ...31 5267 15 2022 PHC 3 MC_0037 Notes...

Страница 32: ...accuracies or omissions it may contain Continuous product improvement may change the product speci cations without notice Therefore Sleipner Group cannot accept liability for any possible differences...

Отзывы: