PHC-3
No.
Name/Value
Description
0101
INSTANCE
Defi nes PHC-3 controller instance.
NONE (default)
Use this for mono hull boats with one PHC-3 controller
PORT
Catamaran use, with PHC-3 at PORT side
STARBOARD
Catamaran use, with PHC-3 at STARBOARD side
0102
THRUSTER CONFIG
Defi nes relationship between control signals and thruster valve outputs.
If thruster is operated in wrong direction, use parameter 2002 to swap bow valve output and parameter
2102 to swap stern valve output.
BOW/STERN (default)
Bow control signal operates bow valve. Stern control signal operates stern valve.
BOW/BOW
Bow control signal operates bow and stern valve as one thruster.
STERN/STERN
Stern control signal operates bow and stern valve as one thruster.
0103
PUMP2 OUTPUT
Defi nes how PUMP2 shutdown valve are operated
DEACTIVATED
PUMP2 output function is deactivated and output is 0V.
ALWAYS ON
PUMP2 output is always on (activated) and pressure from PUMP2 is shutdown.
AUTOMATIC (default)
The system will automatically control load sharing between two PTO pumps by shutting down the second
PTO pump (PUMP2 OUTPUT) when not needed (two PTO pumps/control valves required) to reduce heat
generation in the system and save fuel/energy.
When any thruster is running, both PTO pumps will be active to ensure good performance. When a stabilizer
system is active, PUMP2 OUTPUT will be +12/24V. Second PTO pump is then shutdown to save power. If
stabilizers are active and the stabilizer pressure drops 30% lower than set-point, the system will change
PUMP2 OUTPUT to 0V to wakeup second pump for 15 minutes to increase the flow capacity and maintain
required pressure. After 15 minutes PUMP2 OUTPUT will be reverted to +12/24V (shutdown) unless the
stabilizer pressure is still 30% lower than set-point.
When stabilizer system is turned off, all pumps will be activated (0V).
0104
SYSTEM PRESSURE
Defi nes system pressure sensor type.
INPUT DEACTIVATED
No system pressure sensor connected
ANALOG INPUT (default)
0-400bar pressure sensor (4-20mA)
SWITCH INPUT
Standby pressure switch
Menu - Parameters
MC_0201
Menu - Parameters
For edit parameter press
Enter.
While editing press
Enter to save new value and press Back for cancel editing.
PARAMETERS - 01 Device Settings
4.
4.1
PARAMETERS - 02 Tank Monitor
No.
Name/Value
Description
0201
SENSOR TYPE
Defi nes the oil tank level and temperature sensor type
DEACTIVATED
No tank sensor connected
NC-LEVEL/NC-TEMP
Normally Closed level switch and Normally Closed temp switch
NO-LEVEL/AN-TEMP
Normally Open level switch and analog temp sensor (NTC 10K), part no.: 10 2540 & 10 2542
AN-LEVEL/AN-TEMP
(default)
Analog level sensor (0-180ohm) and analog temp sensor (NTC 10K), part no.: 10 2543
0202
OIL ALARM LEVEL
Sets the oil alarm level
0-100% (default 65%)
Alarm level in steps of 5%
0203
TANK HEIGHT
The height of the oil tank. If tank don’t have flat bottom then measure from center of the tank. This
parameter is important for correct alarm level.
300mm – 15000mm
(default 350mm)
Height in steps of 1mm
0204
OIL LEVEL 100%
Defi nes the 100% oil level from the bottom of the tank. If tank doesn’t have flat bottom then measure from
center of the tank. This parameter is important for correct alarm level.
150mm – 15000mm
(default 270mm)
Level in steps of 1mm
Menu - Parameters