Fault Codes

MC_0117

Fault Code

Description

Cause

Action

10515.0.13

PHC DOUT 6 - Open Circuit

Digital Output 6 is confi gured as crossover and output is open 

circuit

"-Check for open circuit, power consumption  < 5.0 Watt

-Output confi gured wrong, parameter 0506"

10515.0.51

PHC DOUT 6 - Current High

Digital Output 6 current higher than 4.0A

-Check wires and connections for short circuit

10516.0.13

PHC DOUT 3 - Open Circuit

Digital Output 3 is confi gured as crossover and output is open 

circuit

"-Check for open circuit, power consumption  < 5.0 Watt

-Output confi gured wrong, parameter 0503"

10516.0.51

PHC DOUT 3 - Current High

Digital Output 3 current higher than 4.0A

-Check wires and connections for short circuit

10517.0.13

PHC DOUT 2 - Open Circuit

Digital Output 2 is confi gured as crossover and output is open 

circuit

"-Check for open circuit, power consumption < 5.0 Watt

-Output confi gured wrong, parameter 0502"

10517.0.51

PHC DOUT 2 - Current High

Digital Output 2 current higher than 4.0A

-Check wires and connections for short circuit

10518.0.13

PHC DOUT 1 - Open Circuit

Digital Output 1 is confi gured as crossover and output is open 

circuit

"-Check for open circuit, power consumption  < 5.0 Watt

-Output confi gured wrong, parameter 0501"

10518.0.51

PHC DOUT 1 - Current High

Digital Output 1 current higher than 4.0A

-Check wires and connections for short circuit

10519.0.13

PHC DOUT 4 - Open Circuit

Digital Output 4 is confi gured as crossover and output is open 

circuit

"-Check for open circuit, power consumption < 5.0 Watt

-Output confi gured wrong, parameter 0504"

10519.0.51

PHC DOUT 4 - Current High

Digital Output 4 current higher than 4.0A

-Check wires and connections for short circuit

10520.0.51

PHC ECI PUMP POWER FEED - Current High

ECI cooling pump power current higher than 8.0A

"-Check pump cable for damage and short circuits

-Make sure the connector on the cooling pump is correct inserted.

-Replace cooling pump"

10521.0.51

PHC Bow Thruster Power - Current High

Bow thruster PVG feed current higher than 3.0A

-Check PVG wires and connections for short circuit

10522.0.51

PHC Stern Thruster Power - Current High

Stern thruster PVG feed current higher than 3.0A

-Check PVG wires and connections for short circuit

10523.0.51

PHC Thruster Power - Current High

Bow or Stern PVG feed current higher than 3.3A

Check all bow and stern PVG signal wires for short circuits

10524.0.51

PHC ECI Cooling Pump - Current High

ECI cooling pump current higher than 13.0A

"-Check ECI cooling pump cable for damage and short circuits

-Replace ECI cooling pump"

10524.0.53

PHC ECI Cooling Pump - Overvoltage

ECI cooling pump overvoltage, voltage higher than 33.0V

"-Check PHC-3 input voltage is below 33.0V

-Replace ECI cooling pump"

10524.0.54

PHC ECI Cooling Pump - Undervoltage

ECI cooling pump under voltage, voltage is lower than 18.0V

"-Check PHC-3 input voltage is higher than 18.0V

-Replace ECI cooling pump"

10524.0.55

PHC ECI Cooling Pump - Overtemp

ECI cooling pump temperature higher than 100°C (212°F)

"-Check ECI cooling pump for damages

-Replace ECI cooling pump"

10524.0.100

PHC ECI Cooling Pump - No Communication

No communication with ECI cooling pump

"-Check if ECI pump is connected

-Check wires to ECI pump for open circuits

-Check power supply cooling pump

-Wrong cooling pump confi gured, parameter 0301"

10524.0.205

PHC ECI Cooling Pump - HW FAULT

ECI cooling pump hardware fault

-Replace ECI cooling pump

10526.0.0

PHC ECI Cooling Pump Blocked - -

ECI cooling pump is blocked

"-Reset fault and if fault reappears, cooling pump need service or 

replacement.

-Check pump inlet for obstacles"

10527.1.0

PHC VFD Not Ready Instance 1 -

VFD not ready

-VFD external run enable/power available signal is lost.

10528.1.10

PHC VFD ABB Parameter Instance 1 Level Low

ABB ACS550 parameter values 2001 or 2002 cannot be a 

negative value.

-Check ABB ACS550 parameter 2001 and 2002.

10529.0.19

PHC ECI Cooling Pump Speed - Under Limit

ECI pump motor speed under limit. Motor speed is below 100 

rpm, or not getting minimum 750 rpm with in 3 seconds.

"-Check hose for dirt

-Check pump inlet for obstacles"

10530.0.201

PHC PTO ENGINE INSTANCE - INIT FAIL

Parameter 1011-PTO ENGINE INSTANCE is not defi ned

-Set parameter 1011-PTO ENGINE INSTANCE

10531.0.100

CC MODULE - No Communication

No communication with CC Module

"-Check if CC Module is connected

-Check wires to CC Module  for open circuits

-Check power supply CC Module"

10532.0.24

CC MODULE AC PUMP - Fault

The CC Module AC pump curcuit is open and pump is not 

running

"-Check if AC generator is running

-Check if the AC pump contactor is tripped

-Check wires to the pump for open circuit"

10533.0.24

CC MODULE DC PUMP - Fault

The CC Module DC pump curcuit is open and pump is not 

running

"-Check if DC pump contactor has 24VDC

-Check if the DC pump contactor is tripped

-Check wires to the DC pump for open circuit"

36000.1.24

ABB ACS550 Instance 1 Fault

ABB ACS550 fault

Se ABB ACS550 drive for more details

36002.1.24

VACON Instance 1 Fault

VACON VFD Fault

Se VACON drive for more details

36003.1.24

ABB ACS580 Instance 1 Fault

ABB ACS580 fault

Se ABB ACS580 drive for more details

36100.1.100

VFD Instance 1 No Communication

Lost communication with VFD

"-VFD not powered up

-VFD communication cable not connected or incorrectly wired

-On the VFD make sure the RS485 BUS TERMINATION is in ON 

position"

36103.1.0

VFD IN LOCAL Instance 1 -

VFD in local mode

-Switch VFD to remote mode

Содержание PHC-3

Страница 1: ...d Norway www sleipnergroup com DOCUMENT ID REVISION DATE LANGUAGE To download your language go to www sleipnergroup com Including Installation For Hydraulic Proportional Controller PHC 3 5267 15 K e e...

Страница 2: ...Menu Parameters 6 12 Menu Diagnostic 13 16 Menu Operation 17 18 PHC 3 Alarm Descriptions 19 21 Installation Manual Responsibility of the Installer 22 Considerations and Precautions for S Link Systems...

Страница 3: ...display and button interface allow for local con guration of parameters and info LED Status Hydraulic cooling pump output Stabilizer hydraulics connections dump unload PTO main valve Power 24V Power...

Страница 4: ...or run enable signal from power management system OIL TEMP Oil temp and oil level screen will not show if tank monitor sensor type parameter 0201 is deactivated Tank monitor sensor type set to analogu...

Страница 5: ...ive Faults Menu Device INFO MC_0201 MC_0201 FAULTS flashing in upper left corner when any fault has been triggered Go to ACTIVE FAULTS menu for fault details Menu Active Faults Menu Device INFO Device...

Страница 6: ...ad sharing between two PTO pumps by shutting down the second PTO pump PUMP2 OUTPUT when not needed two PTO pumps control valves required to reduce heat generation in the system and save fuel energy Wh...

Страница 7: ...nalog temp sensor NTC 10K part no 10 2543 0202 OIL ALARM LEVEL Sets the oil alarm level 0 100 default 65 Alarm level in steps of 5 0203 TANK HEIGHT The height of the oil tank If tank don t have flat b...

Страница 8: ...PUMP TYPE 800rpm 1600rpm default 1400rpm Speed in steps of 100rpm 0304 POWER SAVE Cooling pump power save function DEACTIVATED POWER SAVE is deactivated and cooling pump will act accordingly to PUMP M...

Страница 9: ...ning 5 5 STERN THRUST ACTIVE Output is activated when stern thruster is running 6 6 ANY THRUST ACTIVE Output is activated when bow or stern thruster is running 7 7 THRUSTER ENABLED Output is activated...

Страница 10: ...nputs is active and all inputs must be deactivated to deactivate the function 0 NOT IN USE default Digital input is not in use and deactivated 1 1 START POWERPACK When the input is activated the AC po...

Страница 11: ...steps of 1 1009 PTO PUMP PRESSURE DETECT LEVEL De nes detection level for PTO standby pressure if parameter 0104 SYSTEM PRESSURE is set to ANALOG INPUT Pressure above level indicates that main engine...

Страница 12: ...he BOW valve output direction for all parameter 0102 THRUSTER CONFIG settings NORMAL default Normal thruster direction SWAPPED Swapped thruster direction 2003 MAX SPOOL TRAVEL Scaling of valves spool...

Страница 13: ...00ms default 200ms In steps of 100ms 2105 RAMP DECREASE De nes the time the output signal uses to go from 100 to 0 100ms 10000ms default 200ms In steps of 100ms 2106 DIRECTION LOCK De nes the time fro...

Страница 14: ...Pressure 4 Set MAX SPOOL TRAVEL parameter 2003 to what Output in shows at maximum thrust and maximum Sys Pressure Shows live update of inputs and outputs related to stern thruster function In Display...

Страница 15: ...0 Volt 1 output is energized When an output is highlighted the output will be toggled as long as the Enter button is being pushed and held In Display Description LS Dump LS Dump Valve Pump 2 Shutdown...

Страница 16: ...A 0bar STAB PRESSURE Stabilizer Pressure in mA 4 0mA 0bar Shows live update of digital inputs 0 input is shorted to 0 Volt activated 1 input is open deactivated Scroll down to view more inputs In Disp...

Страница 17: ...during reception increments the value After every successful reception the value is decremented Tx Error Count Transmit error counter Error during transmit increments the value After every successful...

Страница 18: ...is displayed While VFD is running it is possible to press Back and go to parameters and change parameter values like 1003 PRESSURE SETPOINT or view DIGITAL OUTPUTS Waiting for power management system...

Страница 19: ...DC current 3 1A ECI cooling pump motor peak current 12 4A Hydraulic cooling pump is selected in parameter 0301 and is ready to be operated The following data is shown in this example Hydraulic oil tem...

Страница 20: ...ircuit System pressure sensor open circuit Sensor not connected or wire break Verify system pressure parameter 0104 10503 0 16 PHC System Pressure Short Circuit System pressure sensor short circuit Wi...

Страница 21: ...ECI cooling pump overvoltage voltage higher than 33 0V Check PHC 3 input voltage is below 33 0V Replace ECI cooling pump 10524 0 54 PHC ECI Cooling Pump Undervoltage ECI cooling pump under voltage vo...

Страница 22: ...MC_0105 The installer must read this document to ensure necessary familiarity with the product before installation Instructions in this document cannot be guaranteed to comply with all international a...

Страница 23: ...system and attach using 4 M5x16 screws 2 Attach the required cables to the PHC 3 MC_0431 MG_0485 1 2 Tank sensor cable Black X3 S Link cable X5 Power colling pump cable Blue X1 Hydraulic colling pump...

Страница 24: ...esigned by olekr Copyright All rights reserved SLEIPNER MOTO 120 217 56 Supply Voltage 9 31 VDC Power consumption Less than 1 0 Watt in stand by Digital output 1 to 6 Max load 2 0 Amp pr output Digita...

Страница 25: ...eally be connected around the middle of the BACKBONE Cable to ensure an equal voltage drop at each end of the BACKBONE Cable The yellow and black wire in the POWER Cable shall be connected to GND and...

Страница 26: ...STB SCU GW 1 Panel TP 43A S link Encoder Encoder 1 4 2 SCU Power Supply cable 3 Encoder cable 5 Encoder cable 5 FCU Harness 6 FCU Harness 6 SCU FCU cable 7 SCU FCU cable 7 VFD BUS cable 8 Pump Power...

Страница 27: ...C 3 X1 Harness Part 151470 1 10 Pump power cable Part 10 2371 24v Pump power cable Part 10 2357 hyd MC_0218 IMPORTANT If installing S link products DO NOT connect any other control equipment to the S...

Страница 28: ...rial number ie Thruster AMS PPC etc Bow Bow STB Stern Stern STB Fill in the type location and serial numbers of the S link devices installed Keeping this as a reference will make the setup procedure e...

Страница 29: ...to the Purchaser at the Warrantor s expense If on the other hand the claim is determined to result from circumstances such as described in section 4 above or a result of wear and tear exceeding that...

Страница 30: ...30 5267 15 2022 PHC 3 MC_0037 Notes...

Страница 31: ...31 5267 15 2022 PHC 3 MC_0037 Notes...

Страница 32: ...accuracies or omissions it may contain Continuous product improvement may change the product speci cations without notice Therefore Sleipner Group cannot accept liability for any possible differences...

Отзывы: